www.desatech.com
119426-01F
15
Pipe Cap Tee
Nipple Joint
INSTALLATION
Continued
Figure 15 - Gas Connection
(Thermostatically-Controlled Models Only)
* Purchase the optional CSA design-certified
equipment shutoff valve from your dealer.
See
Accessories
, page 41.
**Minimum inlet pressure for purpose of input
adjustment.
Figure 16 - Gas Connection (Remote-
Ready Models Only)
Gas
Control
Tee Cap Pipe
Joint
Nipple
3" Minimum
Gas
Regulator
PROPANE/LP
From
External Regulator
(11" W.C.** to 14"
W.C. Pressure)
NATURAL
From
Gas Meter (5" W.C.**
to 10.5" W.C.
Pressure)
CSA Design-Certified
Equipment Shutoff Valve
With 1/8" NPT Tap*
Approved
Flexible Gas
Hose (if allowed
by local codes)
Sediment Trap
3" Minimum
Sediment Trap
CSA Design-Certified
Equipment Shutoff Valve
With 1/8" NPT Tap*
Approved Flex ble
Gas Hose (if
allowed by local
codes)
PROPANE/LP
From External
Regulator
(11" W.C.**
to 14" W.C.
Pressure)
NATURAL
From Gas
Meter
(5" W.C.**
to 10.5"
W.C.
Pressure)
WARNING: Use pipe joint
sealant that is resistant to liquid
petroleum (LP) gas.
We recommend that you install a sediment
trap in supply line as shown in Figures 15
or 16, depending on your model. Locate
sediment trap where it is within reach for
cleaning. Install in piping system between
fuel supply and heater. Locate sediment
trap where trapped matter is not likely to
freeze. A sediment trap traps moisture and
contaminants. This keeps them from going
into heater controls. If sediment trap is not
installed or is installed wrong, heater may
not run properly.
CAUTION: Avoid damage to
regulator. Hold gas regulator
with wrench when connecting
it to gas piping and/or fittings
(Thermostatically-Controlled
Models Only).
CAUTION: Avoid damage to
gas control. Hold gas control
with wrench when connecting
it to gas piping and/or fittings
(Remote-Ready Models Only).
CHECKING GAS CONNECTIONS
WARNING: Test all gas piping
and connections, internal and
external to unit, for leaks after
installing or servicing. Correct
all leaks at once.
WARNING: Never use an
open flame to check for a leak.
Apply a noncorrosive leak detec-
tion fluid to all joints. Bubbles
forming show a leak. Correct all
leaks at once.
CAUTION: Make sure exter-
nal regulator has been installed
between propane/LP supply
and heater. See guidelines un-
der
Connecting to Gas Supply
,
page 14.