Test Pressures Equal To or Less Than 1/2 PSIG
1. Close manual shutoff valve (see Figure 15).
2. Pressurize supply piping system by either using compressed air or opening
main gas valve located on or near gas meter.
3. Check all joints from gas meter to manual shutoff valve (see Figure 16). Apply
mixture of liquid soap and water to gas joints. Bubbles forming show a leak.
4. Correct all leaks at once.
Pressure Testing Heater Gas Connections
1. Open manual shutoff valve (see Figure 15).
2. Open main gas valve located on or near gas meter.
3. Make sure control knob of heater is in the OFF position.
4. Check all joints from manual shutoff valve to thermostat gas valve (thermo-
stat-controlled models) or control valve (manually-controlled models) (see
Figure 16). Apply mixture of liquid soap and water to gas joints. Bubbles
forming show a leak.
5. Correct all leaks at once.
6. Light heater (see Operating Heater, pages 22 through 26). Check all other
internal joints for leaks.
7. Turn off heater (see To Turn Off Gas to Appliance, page 24 [thermostat-
controlled models] or page 26 [manually-controlled models]).