background image

www.desatech.com

111347-01F

15

PRESSURE TESTING HEATER GAS 

CONNECTIONS

1.  Open equipment shutoff valve (see Figure 15, 

page 14).

2.  Open main gas valve located on or near gas 

meter for natural gas or open propane/LP 

supply tank valve.

3.  Make sure control knob of heater is in the OFF 

position.

4.  Check all joints from equipment shutoff valve 

to control valve (see Figures 16 and 17). Apply 

noncorrosive leak detection fluid to all joints. 

Bubbles forming show a leak.

5.  Correct all leaks at once.

6.  Light heater (see Operating Heater

, page 16) 

depending on your model). Check all other 

internal joints for leaks.

7.  Turn off heater (see To Turn Off Gas to Ap-

pliance

, page 18 or 20, depending on your 

model).

INSTALLATION

Continued

Figure 16 - Checking Gas Joints 

(Propane/LP only)

Gas Control 
Valve Location

Propane/LP 
Supply Tank

Equipment 
Shutoff Valve

Figure 17 - Checking Gas Joints (Natural 

Gas Only)

Gas Meter

Gas Control 
Valve Location

Equipment 
Shutoff Valve

Figure 18 - Rear Log Placement (Variable 

Manually-Controlled Models)

Rear Log

INSTALLING LOGS

 WARNING: Failure to position 

the parts in accordance with these 

diagrams  or  failure  to  use  only 

parts specifically approved with 

this heater may result in property 

damage or personal injury.

 CAUTION: After installation 

and  periodically  thereafter, 

check  to  ensure  that  no  flame 

comes in contact with any log. 

With the heater set to HI, check 

to see if flames contact any log. If 

so, reposition logs according to 

the log installation instructions 

in this manual. Flames contact

-

ing logs will create soot.

It is very important to install the logs exactly as 

instructed. Do not modify logs. Only use logs 

supplied with heater.

Variable Manually-Controlled Models 
(LSL)

1.  Place rear log onto rear brackets making sure 

brackets fit into recess on bottom of log (see 

Figure 18). 

2.  Place left front log on grate fingers as shown 

in Figure 19, page 16. Place right front log on 

grate fingers and on left front log (see Figure 

19, page 16).

3.  Slide control cover log into position between 

two front logs assuring the cover log seats into 

cutout section (see Figure 20, page 16).

Содержание CDL3924NT

Страница 1: ...n your building Immediatelycallyourgassupplierfromaneighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must...

Страница 2: ...as supplier WARNING This appliance is for installation only in a solid fuel burning mason ry or UL127 factory built fireplaceorinalistedvent lessfireboxenclosure Itis design certified for these instal...

Страница 3: ...enerateschemicals known to the State of California to cause cancer or birth defects or other reproductive harm IMPORTANT Read this owner s manualcarefullyandcompletely before trying to assemble operat...

Страница 4: ...se this heater to cook food or burn paper or other objects 13 Do not use heater if any part has been exposed to or under water Immediately call a qualified service technician to inspect the room heate...

Страница 5: ...ir for proper combustion and ventilation Exhaust fans fireplaces clothes dryers and fuel burning appliances draw air from the house to operate You must provide adequate fresh air for these appliances...

Страница 6: ...ed a part of the unconfined space Adjoining rooms are communicating only if there are doorless passageways or ventilation grills between them DETERMINING FRESH AIR FLOW FOR HEATER LOCATION Determining...

Страница 7: ...as an unconfined space or if the building is of unusually tight construction provide adequate combustion and ventilation air byoneofthemethodsdescribed in the National Fuel Gas Code ANSIZ223 1 NFPA54...

Страница 8: ...lace If not drafting may cause pilot outage or sooting Use a heat resistant sealant Do not seal chimney flue damper WARNING Never install the heater in a bedroom or bathroom unless installed as a vent...

Страница 9: ...Ifso youmustalwaysrunheater with chimney flue damper open If running heater with damper open noncombustible material above fireplace opening is not needed Go to Installing Damper Clamp Accessory for V...

Страница 10: ...opening and mantel shelf If you do not meet the clearances listed below you will need a hood Determining Minimum Mantel Clearance If you meet minimum clearance between mantel shelf and top of fireplac...

Страница 11: ...e and constructed of noncombustible material Ifyourheaterisamanually controlledmodel youmay usethisheaterasaventedproduct Therearethreerea sons for operating your heater in the vented mode 1 Thefirepl...

Страница 12: ...are package provided with heater approved flexible gas hose and fittings not provided if allowed by local codes sealant resistant to propane LP gas not provided electric drill with 3 16 drill bit meta...

Страница 13: ...down Installation Continued as shown in Figure 13 Pointing the vent down protects it from freezing rain or sleet CAUTION Useonlynew black ironorsteelpipe Internally tinned copper tubing may be used in...

Страница 14: ...opening main gas valve located on or near gas meter for natural gas or using compressed air 3 Check all joints from gas meter to equipment shutoff valvefornaturalgasorpropane LPsup ply to equipment sh...

Страница 15: ...Valve Figure 18 Rear Log Placement Variable Manually Controlled Models Rear Log INSTALLING LOGS WARNING Failure to position thepartsinaccordancewiththese diagrams or failure to use only parts specifi...

Страница 16: ...xplosion may result caus ing property damage personal injury or loss of life A This appliance has a pilot which must be lighted by hand When lighting the pilot follow these instructions exactly B BEFO...

Страница 17: ...low B in the safety information page 16 If you don t smell gas go to the next step 6 Slightly depress and turn control knob counterclockwise to the PILOT position Keep control knob pressed in for five...

Страница 18: ...control knob and light pilot with match 3 Keep control knob pressed in for30 seconds after lighting pilot After 30 seconds release control knob Now follow steps 9 and 10 page 17 Thermostat Models FOR...

Страница 19: ...If you don t smell gas go to the next step OPERATING HEATER Continued 5 Turn control knob counterclockwise to the PILOT position Press in control knob for five 5 seconds see Figure 25 Note You may be...

Страница 20: ...pattern Figure 28 shows an incorrect pilot flame pattern The incor rect pilot flame is not touching the thermocouple This will cause the thermocouple to cool When the thermocouple cools the heater wi...

Страница 21: ...f you don t follow directions on the can you could damage the pilot assembly 1 Remove control cover log and front log 2 Shut off the unit including the pilot Allow the unit to cool for at least thirty...

Страница 22: ...ot flame not touching ther mocouple which allows ther mocouple to cool causing pilot flame to go out This problem could be caused by one or both of the following A Low gas pressure B Dirty or partiall...

Страница 23: ...s at burner inlet Periodically repeat as needed 4 Remove blockage TROUBLESHOOTING Continued OBSERVED PROBLEM Burner does not light after ODS pilot is lit Delayed ignition of one or both burners Burner...

Страница 24: ...ce page 21 1 Locate and correct all leaks see Checking Gas Connec tions page 14 2 Replace control valve 1 Take apart gas tubing and remove foreign matter 2 Locate and correct all leaks see Checking Ga...

Страница 25: ...ake sure you tighten the screw after removing the thermostat sensing bulb IMPORTANT Do not force or bend the thermostat sensing bulb or capillary 3 The thermostat sensing bulb may be located to thelow...

Страница 26: ...s For purpose of input adjustment Meadowbrook Oak Log Thermostatically Controlled Btu Variable 26 000 39 000 Type Gas Propane LP Natural Ignition Piezo Manifold Pressure 8 0 W C 3 5 W C Inlet Gas Pres...

Страница 27: ...ssure Is Too Low pilot will not stay lit burners will have delayed ignition heater will not produce specified heat for propane LP units propane LP gas supply may be low Youmayfeelyourgaspressureistool...

Страница 28: ...27 28 1 28 2 28 5 28 4 24 15 16 17 19 18 8 21 26 22 9 4 11 10 28 3 12 20 13 6 20 25 25 25 25 5 7 Illustrated Parts Breakdown Variable Manually Controlled Echo Valley Oak Log Models LSL3124N LSL3124P 3...

Страница 29: ...ral Gas 1 13 099387 08 099387 08 Pilot Tube 1 14 099056 31 099056 26 Injector 1 15 110790 01 110790 01 Left Front Burner Bracket 1 16 110790 02 110790 02 Right Front Burner Bracket 1 17 110793 01 1107...

Страница 30: ...1347 01F 30 ILLUSTRATED PARTS BREAKDOWN Thermostatically Controlled Meadowbrook Oak Log Models CDL3924NT CDL3924PT 15 1 3 4 6 5 12 12 12 20 19 12 16 14 13 2 18 12 12 21 22 23 17 7 11 8 24 1 24 3 24 4...

Страница 31: ...be 1 12 M11084 26 M11084 26 Screw 10 16 x 38 15 13 108631 01 108631 01 Screw 1 Blunt Tip Phillips 2 14 110790 03 110790 03 Rear Burner Bracket 2 15 110790 01 110790 01 Left Front Burner Bracket 1 16 1...

Страница 32: ...The heater MUST be installed by a qualified installer in accordance with all local codes and instructions furnished with the unit This warranty does not apply to parts that are not in original conditi...

Отзывы: