background image

www.desatech.com

111347-01F

6

AIR FOR COMbUSTION 

AND VENTILATION

Continued

Unusually Tight Construction

The air that leaks around doors and windows 

may provide enough fresh air for combustion and 

ventilation. However, in buildings of unusually 

tight construction, you must provide additional 

fresh air.

Unusually tight construction is defined as 

construction where:

a. walls and ceilings exposed to the out

-

side  atmosphere  have  a  continuous 
water vapor retarder with a rating of one 
perm (6 x 10

-11

 kg per pa-sec-m

2

) or less 

with openings gasketed or sealed 

and 

b. weather  stripping  has  been  added  on 

openable windows and doors 

and 

c. caulking or sealants are applied to areas 

such as joints around window and door 
frames, between sole plates and floors, 
between  wall-ceiling  joints,  between 
wall panels, at penetrations for plumb

-

ing, electrical and gas lines and at other 
openings.

If your home meets all of the three criteria 

above, you must provide additional fresh 
air.  See 

Ventilation  Air  From  Outdoors

page 7. 

If your home does not meet all of the three 

criteria  above,  proceed  to 

Determining 

Fresh-Air Flow For Heater Location

.

Confined and Unconfined Space

The National Fuel Gas Code, ANSI Z223.1/NFPA 

54

 defines a confined space as a space whose 

volume is less than 50 cubic feet per 1,000 Btu 

per hour (4.8 m

3

 per kw) of the aggregate input 

rating of all appliances installed in that space and 

an unconfined space as a space whose volume is 

not less than 50 cubic feet per 1,000 Btu per hour 

(4.8 m

3

 per kw) of the aggregate input rating of 

all appliances installed in that space. Rooms com

-

municating directly with the space in which the 

appliances are installed*, through openings not 

furnished with doors, are considered a part of the 

unconfined space.

* Adjoining rooms are communicating only if 

there are doorless passageways or ventilation grills 

between them.

DETERMINING FRESH-AIR FLOW 
FOR HEATER LOCATION

Determining if You Have a Confined or 
Unconfined Space

Use this work sheet to determine if you have a 

confined or unconfined space.

Space:

 Includes the room in which you will install 

heater plus any adjoining rooms with doorless 

passageways or ventilation grills between the 

rooms.

1.  Determine the volume of the space (length x 

width x height).

 

Length x Width x Height =__________cu. ft. 

(volume of space)

 

Example:

 Space size 20 ft. (length) x 16 ft. 

(width) x 8 ft. (ceiling height) = 2560 cu. ft. 

(volume of space)

 

If additional ventilation to adjoining room is 

supplied with grills or openings, add the volume 

of these rooms to the total volume of the space. 

2.  Multiply the space volume by 20 to determine 

the maximum Btu/Hr the space can support.

 

 __________ (volume of space) x 20 = (Maxi-

mum Btu/Hr the space can support)

 

Example:

 2560 cu. ft. (volume of space) x 20 = 

51,200 (maximum Btu/Hr the space can support)

3.  Add the Btu/Hr of all fuel burning appliances in 

the space.

 

Vent-free heater  

 ___________ Btu/Hr

 

Gas water heater* 

 ___________ Btu/Hr

 

Gas furnace 

 ___________ Btu/Hr

 

Vented gas heater 

 ___________ Btu/Hr

 

Gas fireplace logs 

 ___________ Btu/Hr

 

Other gas appliances*  + __________ Btu/Hr

 

Total  

= __________ Btu/Hr

 

* Do not include direct-vent gas appliances. Di-

rect-vent draws combustion air from the outdoors 

and vents to the outdoors.

 

Example:

 

Gas water heater 

__________ Btu/Hr

 

Vent-free fireplace  

+

  ________ Btu/Hr

 

Total 

=  ________ Btu/Hr

4.  Compare the maximum Btu/Hr the space can 

support with the actual amount of Btu/Hr used.

 

 _________Btu/Hr (maximum the space can support) 

 

 _________ Btu/Hr (actual amount of Btu/Hr used)

 

Example:

  51,200 Btu/Hr (maximum the space 

can support) 

 

 

73,000  Btu/Hr  (actual  amount  of 

Btu/Hr used)

40,000

33,000

73,000

Содержание CDL3924NT

Страница 1: ...n your building Immediatelycallyourgassupplierfromaneighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must...

Страница 2: ...as supplier WARNING This appliance is for installation only in a solid fuel burning mason ry or UL127 factory built fireplaceorinalistedvent lessfireboxenclosure Itis design certified for these instal...

Страница 3: ...enerateschemicals known to the State of California to cause cancer or birth defects or other reproductive harm IMPORTANT Read this owner s manualcarefullyandcompletely before trying to assemble operat...

Страница 4: ...se this heater to cook food or burn paper or other objects 13 Do not use heater if any part has been exposed to or under water Immediately call a qualified service technician to inspect the room heate...

Страница 5: ...ir for proper combustion and ventilation Exhaust fans fireplaces clothes dryers and fuel burning appliances draw air from the house to operate You must provide adequate fresh air for these appliances...

Страница 6: ...ed a part of the unconfined space Adjoining rooms are communicating only if there are doorless passageways or ventilation grills between them DETERMINING FRESH AIR FLOW FOR HEATER LOCATION Determining...

Страница 7: ...as an unconfined space or if the building is of unusually tight construction provide adequate combustion and ventilation air byoneofthemethodsdescribed in the National Fuel Gas Code ANSIZ223 1 NFPA54...

Страница 8: ...lace If not drafting may cause pilot outage or sooting Use a heat resistant sealant Do not seal chimney flue damper WARNING Never install the heater in a bedroom or bathroom unless installed as a vent...

Страница 9: ...Ifso youmustalwaysrunheater with chimney flue damper open If running heater with damper open noncombustible material above fireplace opening is not needed Go to Installing Damper Clamp Accessory for V...

Страница 10: ...opening and mantel shelf If you do not meet the clearances listed below you will need a hood Determining Minimum Mantel Clearance If you meet minimum clearance between mantel shelf and top of fireplac...

Страница 11: ...e and constructed of noncombustible material Ifyourheaterisamanually controlledmodel youmay usethisheaterasaventedproduct Therearethreerea sons for operating your heater in the vented mode 1 Thefirepl...

Страница 12: ...are package provided with heater approved flexible gas hose and fittings not provided if allowed by local codes sealant resistant to propane LP gas not provided electric drill with 3 16 drill bit meta...

Страница 13: ...down Installation Continued as shown in Figure 13 Pointing the vent down protects it from freezing rain or sleet CAUTION Useonlynew black ironorsteelpipe Internally tinned copper tubing may be used in...

Страница 14: ...opening main gas valve located on or near gas meter for natural gas or using compressed air 3 Check all joints from gas meter to equipment shutoff valvefornaturalgasorpropane LPsup ply to equipment sh...

Страница 15: ...Valve Figure 18 Rear Log Placement Variable Manually Controlled Models Rear Log INSTALLING LOGS WARNING Failure to position thepartsinaccordancewiththese diagrams or failure to use only parts specifi...

Страница 16: ...xplosion may result caus ing property damage personal injury or loss of life A This appliance has a pilot which must be lighted by hand When lighting the pilot follow these instructions exactly B BEFO...

Страница 17: ...low B in the safety information page 16 If you don t smell gas go to the next step 6 Slightly depress and turn control knob counterclockwise to the PILOT position Keep control knob pressed in for five...

Страница 18: ...control knob and light pilot with match 3 Keep control knob pressed in for30 seconds after lighting pilot After 30 seconds release control knob Now follow steps 9 and 10 page 17 Thermostat Models FOR...

Страница 19: ...If you don t smell gas go to the next step OPERATING HEATER Continued 5 Turn control knob counterclockwise to the PILOT position Press in control knob for five 5 seconds see Figure 25 Note You may be...

Страница 20: ...pattern Figure 28 shows an incorrect pilot flame pattern The incor rect pilot flame is not touching the thermocouple This will cause the thermocouple to cool When the thermocouple cools the heater wi...

Страница 21: ...f you don t follow directions on the can you could damage the pilot assembly 1 Remove control cover log and front log 2 Shut off the unit including the pilot Allow the unit to cool for at least thirty...

Страница 22: ...ot flame not touching ther mocouple which allows ther mocouple to cool causing pilot flame to go out This problem could be caused by one or both of the following A Low gas pressure B Dirty or partiall...

Страница 23: ...s at burner inlet Periodically repeat as needed 4 Remove blockage TROUBLESHOOTING Continued OBSERVED PROBLEM Burner does not light after ODS pilot is lit Delayed ignition of one or both burners Burner...

Страница 24: ...ce page 21 1 Locate and correct all leaks see Checking Gas Connec tions page 14 2 Replace control valve 1 Take apart gas tubing and remove foreign matter 2 Locate and correct all leaks see Checking Ga...

Страница 25: ...ake sure you tighten the screw after removing the thermostat sensing bulb IMPORTANT Do not force or bend the thermostat sensing bulb or capillary 3 The thermostat sensing bulb may be located to thelow...

Страница 26: ...s For purpose of input adjustment Meadowbrook Oak Log Thermostatically Controlled Btu Variable 26 000 39 000 Type Gas Propane LP Natural Ignition Piezo Manifold Pressure 8 0 W C 3 5 W C Inlet Gas Pres...

Страница 27: ...ssure Is Too Low pilot will not stay lit burners will have delayed ignition heater will not produce specified heat for propane LP units propane LP gas supply may be low Youmayfeelyourgaspressureistool...

Страница 28: ...27 28 1 28 2 28 5 28 4 24 15 16 17 19 18 8 21 26 22 9 4 11 10 28 3 12 20 13 6 20 25 25 25 25 5 7 Illustrated Parts Breakdown Variable Manually Controlled Echo Valley Oak Log Models LSL3124N LSL3124P 3...

Страница 29: ...ral Gas 1 13 099387 08 099387 08 Pilot Tube 1 14 099056 31 099056 26 Injector 1 15 110790 01 110790 01 Left Front Burner Bracket 1 16 110790 02 110790 02 Right Front Burner Bracket 1 17 110793 01 1107...

Страница 30: ...1347 01F 30 ILLUSTRATED PARTS BREAKDOWN Thermostatically Controlled Meadowbrook Oak Log Models CDL3924NT CDL3924PT 15 1 3 4 6 5 12 12 12 20 19 12 16 14 13 2 18 12 12 21 22 23 17 7 11 8 24 1 24 3 24 4...

Страница 31: ...be 1 12 M11084 26 M11084 26 Screw 10 16 x 38 15 13 108631 01 108631 01 Screw 1 Blunt Tip Phillips 2 14 110790 03 110790 03 Rear Burner Bracket 2 15 110790 01 110790 01 Left Front Burner Bracket 1 16 1...

Страница 32: ...The heater MUST be installed by a qualified installer in accordance with all local codes and instructions furnished with the unit This warranty does not apply to parts that are not in original conditi...

Отзывы: