www.desatech.com
123721-01E
21
oPeraTioN
Continued
TO TURN OFF GAS
TO APPLIANCE
Shutting Off Fireplace
1. Turn control knob clockwise
to the
OFF position.
2. Turn off all electric power to the appli
-
ance (if applicable) if service is to be
performed.
3. Close equipment shutoff valve (see Figure
19, page 17).
THERMOSTAT CONTROL
OPERATION
The thermostat used on this fireplace senses
the room temperature. At times the room may
exceed the set temperature. If so, the burner will
shut off. The burner will cycle back on when room
temperature drops below the set temperature.
The control knob can be set to any heat level
between HI and LO.
Note: The thermostat sensing bulb measures
the air near the fireplace cabinet. This may
not always agree with room temperature (de
-
pending on housing construction, installation
location, room size, open air temperatures,
etc.). Frequent use of your fireplace will let you
determine your own comfort levels.
MANUAL LIGHTING
PROCEDURE
1. Follow steps 1 through 5 under
Lighting
Instructions
, page 20.
2. With control knob pressed in, strike match.
Hold match to pilot until pilot lights.
3. Keep control knob pressed in for 30 sec
-
onds after lighting pilot. After 30 seconds,
release control knob. Now follow step 8
under
Lighting Instructions
, page 20.
Figure 28 - AUTO/OFF/ON Blower Switch
AUTO/OFF/ON Switch
OPERATING OPTIONAL
BLOWER
This blower has three settings: ON, OFF
and AUTO. In the ON position, the blower
will operate constantly. In the OFF position,
the blower will not operate. In the AUTO
position, the blower will start when the ther
-
mostat senses a sufficient increase in firebox
temperature.
Note: Your fireplace and thermostat blower
will not turn on and off at the same time.
The fireplace may run for several minutes
before the blower turns on. After the heater
modulates to the pilot position, the blower will
continue to run. The blower will shut off after
the firebox temperature decreases.
Note: It is safe to operate fireplace with blower
turned off. However, the blower helps distrib
-
ute heated air from the fireplace.
sPeCiFiCaTioNs
Model CCFPDFT
• Gas Type
Natural
Propane/LP
• Input Max.
26,000 Btu/Hr 26,000 Btu/Hr
• Input Min.
16,000 Btu/Hr 23,000 Btu/Hr
• Manifold Pressure
3.5" W.C.
8" W.C.
• Max. Inlet Pressure 10.5" W.C.
14" W.C.
• Min. Inlet Pressure*
5" W.C.
11" W.C.
*For purposes of input adjustment