VAV T4 RT VAV Zone Controller  

BACnet Communication Module User Guide 

 

 

www.deos-controls.com

 

Page | 7 

 

Object 

Type 

Enabled 

Optional Properties 

Supported 

Writable Properties 

Notes 

  Apdu_Timeout 

  Backup_Failure_Timeout 

  Configuration_Files 

  Last_Restore_Time 

  Backup_And_Restore_State 

  Backup_Preparation_Time 

  Restore_Completion_Time 

  Restore_Preparation_Time

 

  #1001 

  #1002 

  #1003

 

Multi-
State 
Value 

 

  Description 

  Reliability 

  States_Text 

  Priority_Array 

  Relinquish_Default

 

Present_Value 

Some objects are commandable. In such case, the 
priority-array and Relinquish Default properties are 
available. 

Program  

 

  Description 

  Reliability 

Program_Change 

  Only LOAD and RESTART are supported for 

Program Change.  

  Use LOAD to apply the new firmware. 

File 

 

Description 

  Archive 

  File Size

 

Only 0 is the accepted value to be written into file 
size. 

Schedule 

 

  Description 

  Weekly Schedule

 

  Effective Period 

  Weekly Schedule 

  Schedule Default 

  Priority For Writing 

  Out_of_Service

 

 

Out_of_Service Property 

DEOS controllers offer the use of the Out_of_Service writable property. When the value of this property is set to True, 
it  disconnects  the  object  from  the  physical  input,  enabling  you  to  input  other  values.  This  is  useful  for  special 
applications or while troubleshooting. For example, you can ignore the temperature read from a sensor and input the 
desired temperature value in order to perform specific tests. 
For security reasons, a timeout will set the Out_of_Service property back to False after 15 minutes. This value can be 
modified  to  between  0  and  120  minutes  (For  more  information,  see  proprietary  property  #1002  in 

Table  2  -  Device 

Object Properties

). 

 

Содержание VAV T4 RT

Страница 1: ...VAV T4 RT BACnet Guide 170602 docx VAV Zone Controller VAV T4 RT BACnet Communication Module User Guide Zoning System...

Страница 2: ...y of 15 minutes to ensure a Tusage_timeout value within 20 minutes MS TP Support The controller supports a Full Master Node state machine for MS TP The Max_Master and the instances are configured to t...

Страница 3: ...y through the WriteProperty service to Device Object Object_Identifier The device s Object_Identifier is a combination of the Device Object_Type 8 and the Device_Instance 0 4194302 therefore its decim...

Страница 4: ...ot guarantee efficient operation of the controller and other MS TP units on the MS TP network Some MAC address and Max_Master combinations are more efficient than others BACnet requires token passing...

Страница 5: ...figuration of a controller over the network to controllers of the same type using the Copy Config feature 1 Access Operation Mode jumper set to RUN position 2 Press and hold both function buttons for...

Страница 6: ...Max_APDU_Length_Accepted Always 480 Segmentation_Supported 3 No Segmentation APDU_Timeout 6 000 W Number_of_APDU_Retries Always 3 Local_Time 00 00 00 W Local_Date 01 Jan 2015 Thu W UtC_Offset 300 minu...

Страница 7: ...lity Description Min_Present_Value Max_Present_Value Resolution COV Increment Out_of_Service COV Increment Object will automatically return to Normal after a programmable period Refer to Proprietary p...

Страница 8: ...w firmware File Description Archive File Size Only 0 is the accepted value to be written into file size Schedule Description Weekly Schedule Effective Period Weekly Schedule Schedule Default Priority...

Страница 9: ...32 F to 122 F or 0 C to 50 C Resolution 0 02 F 0 01 C Analog Output AO Table 5 Object Table Information Analog Output AO ID Name List Description W Notes AO 1 AnalogOutput1 Integrator Status value th...

Страница 10: ...that represents the reheat demand Read only COV Increment 0 1 0 to 100 Resolution 0 1 AV 24 Cfg_DuctReheatPropBand Advanced Configuration value that represents the range through which the controller...

Страница 11: ...ue represents the maximum control signal of the controlled element If the signal is 0 to 10Vdc or 2 to 10Vdc then the maximum value is 10 Volts It can also be used to limit the maximum output of the c...

Страница 12: ...low Balance Instructions Present Value COV Increment 1 0 to 9 995 No units Resolution 1 No unit Writable only if system is in balancing mode AV 114 Cfg_AirFlowOffset Integrator Configuration value use...

Страница 13: ...1 unit Binary Input BI Table 7 Object Table Information Binary Input BI ID Name List Description W Notes BI 1 DigitalInput1 Integrator Contact status of the input 0 Open 1 Close Out_of_Service 0 Open...

Страница 14: ...tuator is configured to open from 0 to 90 When set to 1 Reverse the damper actuator is configured to open from 90 to 0 When this value is changed the controller will execute an auto stroke to reset th...

Страница 15: ...ale is used for low airflows up to 999 Scale 100 Airflow is multiplied by 100 This scale is used for very low airflows up to 99 Present Value Scale1 Scale10 Scale100 MSV 42 AirFlowBal_Mode Integrator...

Страница 16: ...and Demand Temp only Setpoint only Off MSV 100 Cfg_ObjectList Integrator Configuration value of the object list Integrator Object list restricted to Integrator Object List Advanced Object list restric...

Отзывы: