VAV T4 RT VAV Zone Controller  

BACnet Communication Module User Guide 

 

 

www.deos-controls.com

 

Page | 2 

 

BACnet Properties Configuration 

To establish communication on the network, and guarantee a unique ID of devices in a BACnet system, the following 
properties may have to be configured.  

Table 1 - BACnet Properties Configuration 

Property 

Default Value 

Configuration 

MAC Address 

000 

 

Set to a unique address on the network between 000 and 254. 

 

The value can be set manually via the menu. 

 

The value can be set manually through the 

WriteProperty

 service to 

Device Object.proprietary-property#1000 MSTP-Address

 

The values from 128-254 represent MS/TP non-token passing slave 
devices. 

Device Instance 

Auto 

 

The controller automatically configures its device instance to 877,000 + 
MAC address.  

 

The value can be set manually via the menu. 

 

The value can be set manually through the 

WriteProperty

 service to 

Device Object.Object_Identifier

.  

 

The device’s 

Object_Identifier

 is a combination of the 

Device 

Object_Type

 (8) and the 

Device_Instance

 (0-4194302), therefore its 

decimal or hexadecimal representation tends to be incomprehensible. 

 

For example, the 

Device_Instance

=1000 has an equivalent 

Object_Identifier

 of 0x020003E8 hexadecimal or 33555432 decimal. 

Baud Rate 

0 = Auto 

 

The controller configures its baud rate automatically by detecting the 
network upon connection. 

 

The value can be set manually from the available values of (0) Auto, 9600, 
19200, 38400, and 76800. 

Max_Master 

127 

 

Configure 

Max_Master

 value to increase network efficiency when there are 

less than 127 devices on the network.  

 

The 

Max_Master

 value can be changed through the 

WriteProperty 

service 

to

 Device

 

Object.Max_Master

For more information, refer to the

 

MAC Address and Max_Master

 

section.  

Device Object.Object_Name 

Name of the 
device 

 

Configure the name of the device through the 

WriteProperty 

service to 

Device Object.Object_Name

. For example, 

VAV T4 RT

 

 

 

Содержание VAV T4 RT

Страница 1: ...VAV T4 RT BACnet Guide 170602 docx VAV Zone Controller VAV T4 RT BACnet Communication Module User Guide Zoning System...

Страница 2: ...y of 15 minutes to ensure a Tusage_timeout value within 20 minutes MS TP Support The controller supports a Full Master Node state machine for MS TP The Max_Master and the instances are configured to t...

Страница 3: ...y through the WriteProperty service to Device Object Object_Identifier The device s Object_Identifier is a combination of the Device Object_Type 8 and the Device_Instance 0 4194302 therefore its decim...

Страница 4: ...ot guarantee efficient operation of the controller and other MS TP units on the MS TP network Some MAC address and Max_Master combinations are more efficient than others BACnet requires token passing...

Страница 5: ...figuration of a controller over the network to controllers of the same type using the Copy Config feature 1 Access Operation Mode jumper set to RUN position 2 Press and hold both function buttons for...

Страница 6: ...Max_APDU_Length_Accepted Always 480 Segmentation_Supported 3 No Segmentation APDU_Timeout 6 000 W Number_of_APDU_Retries Always 3 Local_Time 00 00 00 W Local_Date 01 Jan 2015 Thu W UtC_Offset 300 minu...

Страница 7: ...lity Description Min_Present_Value Max_Present_Value Resolution COV Increment Out_of_Service COV Increment Object will automatically return to Normal after a programmable period Refer to Proprietary p...

Страница 8: ...w firmware File Description Archive File Size Only 0 is the accepted value to be written into file size Schedule Description Weekly Schedule Effective Period Weekly Schedule Schedule Default Priority...

Страница 9: ...32 F to 122 F or 0 C to 50 C Resolution 0 02 F 0 01 C Analog Output AO Table 5 Object Table Information Analog Output AO ID Name List Description W Notes AO 1 AnalogOutput1 Integrator Status value th...

Страница 10: ...that represents the reheat demand Read only COV Increment 0 1 0 to 100 Resolution 0 1 AV 24 Cfg_DuctReheatPropBand Advanced Configuration value that represents the range through which the controller...

Страница 11: ...ue represents the maximum control signal of the controlled element If the signal is 0 to 10Vdc or 2 to 10Vdc then the maximum value is 10 Volts It can also be used to limit the maximum output of the c...

Страница 12: ...low Balance Instructions Present Value COV Increment 1 0 to 9 995 No units Resolution 1 No unit Writable only if system is in balancing mode AV 114 Cfg_AirFlowOffset Integrator Configuration value use...

Страница 13: ...1 unit Binary Input BI Table 7 Object Table Information Binary Input BI ID Name List Description W Notes BI 1 DigitalInput1 Integrator Contact status of the input 0 Open 1 Close Out_of_Service 0 Open...

Страница 14: ...tuator is configured to open from 0 to 90 When set to 1 Reverse the damper actuator is configured to open from 90 to 0 When this value is changed the controller will execute an auto stroke to reset th...

Страница 15: ...ale is used for low airflows up to 999 Scale 100 Airflow is multiplied by 100 This scale is used for very low airflows up to 99 Present Value Scale1 Scale10 Scale100 MSV 42 AirFlowBal_Mode Integrator...

Страница 16: ...and Demand Temp only Setpoint only Off MSV 100 Cfg_ObjectList Integrator Configuration value of the object list Integrator Object list restricted to Integrator Object List Advanced Object list restric...