VAV T4 RT VAV Zone Controller  

BACnet Communication Module User Guide 

 

 

www.deos-controls.com

 

Page | 6 

 

Property 

Value 

Writable 

Proprietary property #1000 

  Programmable (default:0) 

  Represents the MS/TP MAC address in the range of 0 to 254  

  Values 128 to 254 represent MS/TP non-token passing slave devices 

Proprietary property #1001 

  Programmable (default: Auto) 

  Represents the MS/TP Baud rate (unsigned type) 

  Values are 0 (Auto), 9600, 19200, 38400, and 76800 

  Reading this property always returns the actual Baud rate 

Proprietary property #1002 

  Programmable (default: 15 minutes) 

  Represents the period of time that an object in/out of service will automatically 

return to normal. Range = 0 to120 minutes (unsigned type) 

  Writing 0 means no automatic return to normal 

Proprietary property #1003 

  0 = Mode ZNB, 1 = Mode VAV 

 

Object Types Supported 

The following table lists all the BACnet properties supported for each object type. Most of the  properties are locked. 
The exception is 

Present_Value

, which represents the dynamic operating values of the device, and the Status_Flag, 

Event_State

,

 and Reliability properties, which reflect the availability of the 

Present_Value

. Unless otherwise specified, 

properties are not changeable. 

Table 3 - Object Types Supported 

Object 

Type 

Enabled 

Optional Properties 

Supported 

Writable Properties 

Notes 

Note: Writable properties are different for some objects. Refer to the respective Object Table information to know the writable property for objects.

 

Analog 
Input 

 

  Reliability 

  Description 

  Min_Present_Value 

  Max_Present_Value 

  Resolution 

  COV-Increment 

  Out_of_Service 

  COV-Increment 

Object will automatically return to Normal after a 
programmable period. Refer to Proprietary property 
#1002 of Device Object in Table 2 - Device Object 
Properties.

 

Analog 
Value 

 

  Reliability 

  Description 

  COV-Increment 

  Priority_Array 

  Relinquish_Default

 

  Present_Value  

  Out_of_Service 

  COV-Increment 

  Refer to Out_of_Service Property section on page 

7 for more information.  

  Object will automatically return to Normal after a 

programmable period. Refer to Proprietary 
property #1002 of Device Object in Table 2 - 
Device Object Properties.  

Analog 
Output 

 

  Description 

  Reliability 

  Min-Pres-Value 

  Max-Pres-Value 

  Resolution 

  COV-Increment 

  Present_Value  

  COV-Increment 

 

Binary 
Input 

 

  Reliability 

  Active_Text 

  Inactive_Text 

  Description 

Out_of_Service 

Object will automatically return to Normal after a 
programmable period. Refer to Proprietary property 
#1002 of Device Object in Table 2 - Device Object 
Properties. 

Binary 
Value 

 

  Reliability 

  Active_Text 

  Inactive_Text 

  Description 

  Priority_Array 

  Relinquish_Default

 

  Present_Value 

  Out_of_Service 

 

 

Object automatically returns to Normal after a 
programmable time. Refer to Proprietary property 
#1002 of Device Object in Table 2 - Device Object 
Properties.  

Binary 
Output 

 

  Description 

  Reliability 

  Inactive-text 

  Active-text 

Present_Value 

 

 

Device 

 

  Max_Master 

  Max_Info_Frame 

  Description 

  active-COV-subscriptions 

  #1000 (MSTP addr)

 

  #1001 (Baud rate) 

  #1002 (Time out) 

  Local_Time 

  Local_Date 

  UTC_Offset  

  Daylight_Savings_Status 

  Object_Identifier 

  Object_Name 

  Max_Master 

  Description 

  Local_Time 

  Local_Date 

  UTC_Offset  

  Daylight_Savings_Status 

  Apdu_Timeout 

  Backup_Failure_Timeout 

  #1000  

 

Содержание VAV T4 RT

Страница 1: ...VAV T4 RT BACnet Guide 170602 docx VAV Zone Controller VAV T4 RT BACnet Communication Module User Guide Zoning System...

Страница 2: ...y of 15 minutes to ensure a Tusage_timeout value within 20 minutes MS TP Support The controller supports a Full Master Node state machine for MS TP The Max_Master and the instances are configured to t...

Страница 3: ...y through the WriteProperty service to Device Object Object_Identifier The device s Object_Identifier is a combination of the Device Object_Type 8 and the Device_Instance 0 4194302 therefore its decim...

Страница 4: ...ot guarantee efficient operation of the controller and other MS TP units on the MS TP network Some MAC address and Max_Master combinations are more efficient than others BACnet requires token passing...

Страница 5: ...figuration of a controller over the network to controllers of the same type using the Copy Config feature 1 Access Operation Mode jumper set to RUN position 2 Press and hold both function buttons for...

Страница 6: ...Max_APDU_Length_Accepted Always 480 Segmentation_Supported 3 No Segmentation APDU_Timeout 6 000 W Number_of_APDU_Retries Always 3 Local_Time 00 00 00 W Local_Date 01 Jan 2015 Thu W UtC_Offset 300 minu...

Страница 7: ...lity Description Min_Present_Value Max_Present_Value Resolution COV Increment Out_of_Service COV Increment Object will automatically return to Normal after a programmable period Refer to Proprietary p...

Страница 8: ...w firmware File Description Archive File Size Only 0 is the accepted value to be written into file size Schedule Description Weekly Schedule Effective Period Weekly Schedule Schedule Default Priority...

Страница 9: ...32 F to 122 F or 0 C to 50 C Resolution 0 02 F 0 01 C Analog Output AO Table 5 Object Table Information Analog Output AO ID Name List Description W Notes AO 1 AnalogOutput1 Integrator Status value th...

Страница 10: ...that represents the reheat demand Read only COV Increment 0 1 0 to 100 Resolution 0 1 AV 24 Cfg_DuctReheatPropBand Advanced Configuration value that represents the range through which the controller...

Страница 11: ...ue represents the maximum control signal of the controlled element If the signal is 0 to 10Vdc or 2 to 10Vdc then the maximum value is 10 Volts It can also be used to limit the maximum output of the c...

Страница 12: ...low Balance Instructions Present Value COV Increment 1 0 to 9 995 No units Resolution 1 No unit Writable only if system is in balancing mode AV 114 Cfg_AirFlowOffset Integrator Configuration value use...

Страница 13: ...1 unit Binary Input BI Table 7 Object Table Information Binary Input BI ID Name List Description W Notes BI 1 DigitalInput1 Integrator Contact status of the input 0 Open 1 Close Out_of_Service 0 Open...

Страница 14: ...tuator is configured to open from 0 to 90 When set to 1 Reverse the damper actuator is configured to open from 90 to 0 When this value is changed the controller will execute an auto stroke to reset th...

Страница 15: ...ale is used for low airflows up to 999 Scale 100 Airflow is multiplied by 100 This scale is used for very low airflows up to 99 Present Value Scale1 Scale10 Scale100 MSV 42 AirFlowBal_Mode Integrator...

Страница 16: ...and Demand Temp only Setpoint only Off MSV 100 Cfg_ObjectList Integrator Configuration value of the object list Integrator Object list restricted to Integrator Object List Advanced Object list restric...

Отзывы: