DEOS VAV T4 RT Скачать руководство пользователя страница 2

 

VAV T4 RT VAV Zone Controller  

BACnet Communication Module User Guide 

 

 

www.deos-controls.com

 

Page | 1 

 

Introduction  

The VAV T4 RT VAV Zone Controller BACnet

®

 Communication Module User Guide provides information about using 

the  controllers  in  the  zoning  system  with  BACnet  communications  feature.  The  BACnet  communication  protocol  for 
building  automation  and  control  networks  enables  communication  between  client  devices  within  a  network.  The 
controller provides a BACnet network interface between BACnet client devices and DEOS Controller series devices. It 
uses the BACnet Master Slave/Token Passing (MS/TP) protocol at the BACnet MAC layer. 

Pre-requisites 

The  BACnet  communication  user  guide  assumes  that  you  are  familiar  with  the  concepts  of  BACnet  and  its 
terminology. 

Advantages of BACnet  

BACnet enabled controllers have the following advantages: 

 

Quick  Message  Transmission.

  The  controller  uses  a  synchronous  implementation  for  BACnet  messages 

making  it  quick  and  efficient.  Each  BACnet  confirmed  service  request  is  answered  as  quickly  as  possible 
without using the 

Reply  Postponed

 frame. The MS/TP implementation is performed within 

Tusage_delay

 of 

15 minutes to ensure a 

Tusage_timeout

 value within 20 minutes.  

 

MS/TP  Support.

  The  controller  supports  a  Full  Master  Node  state machine  for  MS/TP.  The  Max_Master  and 

the  instances  are  configured  to the  device  object  through 

BACnet  WriteProperty

  service  or  via  the  device's 

Programming Mode. The  MAC address  and  the MS/TP  baud rate setting  of  9600,  19200, 38400,  and 76800 
are  also  set  through  the 

BACnet  Write  Property 

service  or  via  the  device's  Programming  Mode.  In 

Programming 

mode,  the  device  is  configured  through  the  device’s  keypad.  For  more  information  about  the 

WriteProperty, refer to 

Table 3 - Object Types Supported

 

BIBB  Support

.  The  controller  functions  the  same  way  as  the  B-ASC  type  profile  server  and  supports  the 

specific BIBB as per their relevant definitions. 

o

 

DS-RP-B 

o

 

DS-RPM-B 

o

 

DS-WP-B 

o

 

DS-WPM-B 

o

 

DM-DCC-B 

o

 

DM-DDB-B 

o

 

DM-DOB-B 

o

 

DM-RD-B 

o

 

DM-TS-B 

o

 

DM-UTC-B 

o

 

DS-COV-B 

o

 

DS-COVP-B 

o

 

SCHED-WS-I-B 

 

Object Support

. The controller supports a fixed list of BACnet visible values, which appear as Present_Values 

of various BACnet standard object types in addition to a device object. For more information, refer to 

Table 3 - 

Object Types Supported

.  

 

Alarms

. The controller supports indication of  various  alarm conditions through  value changes  in properties of 

several objects. However, it does not generate BACnet event notifications.  

 

 

 

Содержание VAV T4 RT

Страница 1: ...VAV T4 RT BACnet Guide 170602 docx VAV Zone Controller VAV T4 RT BACnet Communication Module User Guide Zoning System...

Страница 2: ...y of 15 minutes to ensure a Tusage_timeout value within 20 minutes MS TP Support The controller supports a Full Master Node state machine for MS TP The Max_Master and the instances are configured to t...

Страница 3: ...y through the WriteProperty service to Device Object Object_Identifier The device s Object_Identifier is a combination of the Device Object_Type 8 and the Device_Instance 0 4194302 therefore its decim...

Страница 4: ...ot guarantee efficient operation of the controller and other MS TP units on the MS TP network Some MAC address and Max_Master combinations are more efficient than others BACnet requires token passing...

Страница 5: ...figuration of a controller over the network to controllers of the same type using the Copy Config feature 1 Access Operation Mode jumper set to RUN position 2 Press and hold both function buttons for...

Страница 6: ...Max_APDU_Length_Accepted Always 480 Segmentation_Supported 3 No Segmentation APDU_Timeout 6 000 W Number_of_APDU_Retries Always 3 Local_Time 00 00 00 W Local_Date 01 Jan 2015 Thu W UtC_Offset 300 minu...

Страница 7: ...lity Description Min_Present_Value Max_Present_Value Resolution COV Increment Out_of_Service COV Increment Object will automatically return to Normal after a programmable period Refer to Proprietary p...

Страница 8: ...w firmware File Description Archive File Size Only 0 is the accepted value to be written into file size Schedule Description Weekly Schedule Effective Period Weekly Schedule Schedule Default Priority...

Страница 9: ...32 F to 122 F or 0 C to 50 C Resolution 0 02 F 0 01 C Analog Output AO Table 5 Object Table Information Analog Output AO ID Name List Description W Notes AO 1 AnalogOutput1 Integrator Status value th...

Страница 10: ...that represents the reheat demand Read only COV Increment 0 1 0 to 100 Resolution 0 1 AV 24 Cfg_DuctReheatPropBand Advanced Configuration value that represents the range through which the controller...

Страница 11: ...ue represents the maximum control signal of the controlled element If the signal is 0 to 10Vdc or 2 to 10Vdc then the maximum value is 10 Volts It can also be used to limit the maximum output of the c...

Страница 12: ...low Balance Instructions Present Value COV Increment 1 0 to 9 995 No units Resolution 1 No unit Writable only if system is in balancing mode AV 114 Cfg_AirFlowOffset Integrator Configuration value use...

Страница 13: ...1 unit Binary Input BI Table 7 Object Table Information Binary Input BI ID Name List Description W Notes BI 1 DigitalInput1 Integrator Contact status of the input 0 Open 1 Close Out_of_Service 0 Open...

Страница 14: ...tuator is configured to open from 0 to 90 When set to 1 Reverse the damper actuator is configured to open from 90 to 0 When this value is changed the controller will execute an auto stroke to reset th...

Страница 15: ...ale is used for low airflows up to 999 Scale 100 Airflow is multiplied by 100 This scale is used for very low airflows up to 99 Present Value Scale1 Scale10 Scale100 MSV 42 AirFlowBal_Mode Integrator...

Страница 16: ...and Demand Temp only Setpoint only Off MSV 100 Cfg_ObjectList Integrator Configuration value of the object list Integrator Object list restricted to Integrator Object List Advanced Object list restric...

Отзывы: