VAV T4 RT VAV Zone Controller    

BACnet Communication Module User Guide 

 

 

www.deos-controls.com

 

Page | 15 

 

ID 

Name 

List 

Description 

W? 

Notes 

1StageOnOff

: BO1 stage 1 on off is used.  

1StagePulsed

: BO1 stage 1 pulsing is used 

2StagesOnOff

: BO1 and BO2 2 stages on off are used. 

3StagesOnOff

: BO1, BO2, BO3 3 stages on off are used. 

1StagePulsed 

 2StagesOnOff 

 3StagesOnOff 

MSV.52 

Cfg_PerimeterReheat 

Integrator 

Select the configuration of perimeter reheat output (AO2 or BO4). 

No

: Duct reheat is not used. 

AnalogOutputDA

: Direct Acting AO2 is used. 

AnalogOutputRA

: Reverse Acting AO2 is used. 

1StageOnOff

: BO4 1 stage on off is used. 

1StagePulsed

: BO4 1 stage pulsing is used. 

Present Value 

No 

AnalogOutputDA 

AnalogOutputRA 
1StageOnOff 
1StagePulsed 

MSV.95 

Cfg_DisplayInfo 

Advanced 

Configuration value of the information displayed on the TRL. 

Display Temp Demand

: TRL will display the actual temperature and 

cooling/heating demand. 

Display Setpoint Demand

: TRL will display the actual setpoint and 

cooling/heating demand. 

Display Temp

: TRL will display the actual temperature but no demand. 

Display Setpoint

: TRL will display the actual setpoint but no demand. 

Display Off

: TRL display will be off (no display). 

Present Value 

Temp and Demand  

Setpoint and Demand 

Temp only 

 Setpoint only 

Off  

MSV.100  Cfg_ObjectList 

Integrator 

Configuration value of the object list.  

Integrator

: Object list restricted to Integrator Object List 

Advanced

: Object list restricted to Integrator and Advanced Object List 

Factory

: Complete object list is available. 

Present Value 

Integrator object list 

Advanced object list 

Factory object list 

MSV.101  Cfg_KeypadLockoutLevels 

Integrator 

Configurations to limit the user’s access to change setpoints, modes, and 
passwords. This is represented in a level format. 

Level 0

: No lockouts  

Level 1

: Arrow buttons locked 

Level 2

: Arrow buttons and mode locked   

Level 3

: Arrow buttons, mode, and password menu locked 

Level 4

: Arrow buttons, mode, password menu and program mode locked 

Present Value 

Level 0 

Level 1 

Level 2 

Level 3 

Level 3 

Other  

ID 

Name 

List 

Description 

W? 

Notes 

PGM.1 

ProgramFirmware 

Integrator 

Program firmware. Set to LOAD to program the file in application memory. The 
controller will be reset and the firmware will be LOADED into the memory. Use 
only the binary file provided by DEOS. 

Program Change 

Program Change, only LOAD (1) and RESTART 
(4) are supported 

FIL.1 

FirmwareBinaryFile 

Integrator 

Firmware binary file. Set to LOAD to program the file in application memory. 
The controller will be reset and the firmware will be LOADED into the memory. 
Use only the binary file provided by DEOS. 

File Size  

Archive 

File Size is accepted for 0 value only. 

 

Содержание VAV T4 RT

Страница 1: ...VAV T4 RT BACnet Guide 170602 docx VAV Zone Controller VAV T4 RT BACnet Communication Module User Guide Zoning System...

Страница 2: ...y of 15 minutes to ensure a Tusage_timeout value within 20 minutes MS TP Support The controller supports a Full Master Node state machine for MS TP The Max_Master and the instances are configured to t...

Страница 3: ...y through the WriteProperty service to Device Object Object_Identifier The device s Object_Identifier is a combination of the Device Object_Type 8 and the Device_Instance 0 4194302 therefore its decim...

Страница 4: ...ot guarantee efficient operation of the controller and other MS TP units on the MS TP network Some MAC address and Max_Master combinations are more efficient than others BACnet requires token passing...

Страница 5: ...figuration of a controller over the network to controllers of the same type using the Copy Config feature 1 Access Operation Mode jumper set to RUN position 2 Press and hold both function buttons for...

Страница 6: ...Max_APDU_Length_Accepted Always 480 Segmentation_Supported 3 No Segmentation APDU_Timeout 6 000 W Number_of_APDU_Retries Always 3 Local_Time 00 00 00 W Local_Date 01 Jan 2015 Thu W UtC_Offset 300 minu...

Страница 7: ...lity Description Min_Present_Value Max_Present_Value Resolution COV Increment Out_of_Service COV Increment Object will automatically return to Normal after a programmable period Refer to Proprietary p...

Страница 8: ...w firmware File Description Archive File Size Only 0 is the accepted value to be written into file size Schedule Description Weekly Schedule Effective Period Weekly Schedule Schedule Default Priority...

Страница 9: ...32 F to 122 F or 0 C to 50 C Resolution 0 02 F 0 01 C Analog Output AO Table 5 Object Table Information Analog Output AO ID Name List Description W Notes AO 1 AnalogOutput1 Integrator Status value th...

Страница 10: ...that represents the reheat demand Read only COV Increment 0 1 0 to 100 Resolution 0 1 AV 24 Cfg_DuctReheatPropBand Advanced Configuration value that represents the range through which the controller...

Страница 11: ...ue represents the maximum control signal of the controlled element If the signal is 0 to 10Vdc or 2 to 10Vdc then the maximum value is 10 Volts It can also be used to limit the maximum output of the c...

Страница 12: ...low Balance Instructions Present Value COV Increment 1 0 to 9 995 No units Resolution 1 No unit Writable only if system is in balancing mode AV 114 Cfg_AirFlowOffset Integrator Configuration value use...

Страница 13: ...1 unit Binary Input BI Table 7 Object Table Information Binary Input BI ID Name List Description W Notes BI 1 DigitalInput1 Integrator Contact status of the input 0 Open 1 Close Out_of_Service 0 Open...

Страница 14: ...tuator is configured to open from 0 to 90 When set to 1 Reverse the damper actuator is configured to open from 90 to 0 When this value is changed the controller will execute an auto stroke to reset th...

Страница 15: ...ale is used for low airflows up to 999 Scale 100 Airflow is multiplied by 100 This scale is used for very low airflows up to 99 Present Value Scale1 Scale10 Scale100 MSV 42 AirFlowBal_Mode Integrator...

Страница 16: ...and Demand Temp only Setpoint only Off MSV 100 Cfg_ObjectList Integrator Configuration value of the object list Integrator Object list restricted to Integrator Object List Advanced Object list restric...

Отзывы: