DAEnetIP2
User Manual
12 Sep 2013
6.3.3.
Mode “Low/High”
The output will be set if the input level is out of the range with High and Low
Threshold.
6.3.4.
Mode “Acc”
The output will be set if the input level is less than Low Threshold and will be in old
state after input level is over High Threshold.
This function does not affect to SNMP traps but the same Threshold values are
used for sending SNMP traps.
Additionally in firmware ver. 4.097 there is option "INV" (Inversion) - it reverse the
signal level which is generated to P5 (if the regular was to set in "1" during INV it will
be "0". For example if temperature sensor is used - this option allows to be done
automatic switch ON of load when the temperature is higher than the threshold HIGH
(and switch OFF when the temperature is lower than the threshold LOW). And it is
possible the opposite (without "INV") it is possible heating during low temperatures
(for instance antennas) - the output is ON when level is lower than LOW and OFF
when the level is higher than HIGH.
SNMP: Changing the value in respective ромяна aevPinX.0. The possible values
are: None, Low, High, LowHigh, Acc
Web: Menu „SNMP traps-> P5 set at”
6.4.
I/O Ports
Figure 11. I/O ports web page
P3 and P5 are configurable digital I/O port (0-3.3VDC). It is possible to be
configured by the user for its own purposes - digital inputs or outputs.
P6 is 8 channel 10 bit analog input port. The reference voltage is 3.3VDC (from
power supply source)
-
19
-