6.3. General Settings
Figure 6.5.
General Settings
Inputs Pull-ups -
enable pull-up resistors for P3/P5 ports when they are configured as
digital inputs;
SNMP: cfgPortPullUps.0
Save Outputs -
when checked, each time the relays state is changed, it will be saved in
non-volatile memory (EEPROM), so after reboot/restart it will be restored;
This option should be used with care in dynamic systems because of restriction in maximum write
cycles of the EEPROM (usually 100 000 write/erase cycles).
Digital Inputs Filter, ms
– digital inputs filter constant. The range is from 0 up to 200 ms.
The filter is disabled when its value is set to 0;
This parameter sets a low pass software filter that removes the short-term fluctuations from the
input signal and reduces the effect of occasional spikes. Note that the higher filter constants give a
slower response to changes.
Analog Inputs Filter, sec
– analog inputs filter constant. The range is from 0 up to 30 sec.
The filter is disabled when its value is set to 0;
This parameter sets a low pass software filter that removes the short-term fluctuations from the
input signal and reduces the effect of occasional spikes. Note that the higher filter constants give a
slower response to changes.