NO.6 Detailed Function Description
48
6.5 Functional parameters of multi-segment speed
P080
Setting range
Unit
Ex-factory value
Alteration
Operation mode selection
1-5
1
0
╳
0: Common operation refers to operation in a commonly controlled way.
1: Internally controlled multi-segment speed (16-segment speed)
[Description] 1) 16-segment speed is composed by main speed and 15-segment
speed;
2) Acceleration/deceleration time of each segment speed is set through P084 and
P085;
3) Operating time is set by timers P101-P116 and timers for unused control segments
are set as 0;
4) Operating direction of each segment speed is set through P082 and P083;
5) Under operation of internally controlled multi-segment speed, operating time and
direction is dependent on the setting of internal parameters, with invalid external time
and forward/reverse switching.
2: Externally controlled 4-segment speed (refer to function description for high-speed,
medium-speed and low-speed terminals P044-P049)
3: Externally controlled 16-segment speed
Multi-function digital input terminal
Result
Multi-s
egmen
t speed
I
Multi
-seg
ment
spee
d II
Multi-s
egmen
t speed
III
Multi
-seg
ment
spee
d IV
OFF
OFF
OFF
OFF
Main frequency
ON
OFF
OFF
OFF
For multi-segment speed II, the frequency is
determined by P086
OFF
ON
OFF
OFF
For multi-segment speed III, the frequency is
determined by P087
ON
ON
OFF
OFF
For multi-segment speed IV, the frequency is
determined by P088
OFF
OFF
ON
OFF
For multi-segment speed V, the frequency is
determined by P089