NO.6 Detailed Function Description
47
(4) Parameters: P073=10 P075=1 P072=40 P074=0 P076=0
[Description] This curve is an extended one of the above curve. 2V-10V (4.8mA-20mA)
is corresponding to 0Hz-40Hz and signals of 0V-2V (4-4.8mA) are invalid. The curve
can be used to avoid noise disturbance. Under severe environment, signals under 1V
shall not be used as far as possible to set operating frequency of the inverter.
P077
Setting range
Unit
Ex-factory value
Alteration
Memory function selection
for UP and DOWN
0-1
1
0
╳
0: Not memorized
1: Memorized
This parameter can be used to select whether the value modified through UP and DOWN is
memorized or not after stop. When P077 is set as 1, the value upon stop will be memorized
after re-startup; when P077 is set as 0 or the inverter is restarted after power failure, the
value modified through UP and DOWN as well as the value whose frequency is set as P003
will not be memorized.
Refer to P044-P049 description for details about related parameters.
P078
Setting range
Unit
Ex-factory value
Alteration
Increment selection
For UP and DOWN
0-1
1
0
╳
0: For 0.01HZ, minimum up/down speed is 0.01HZ
1: For 0.1HZ, minimum up/down speed is 0.1HZ
This parameter can be used to adjust up/down speed unit for UP and DOWN to meet users'
need.
P079
Setting range
Unit
Ex-factory value
Alteration
Increment multiple for
UP and DOWN
1-250
1
0
╳
The actual increment of UP and DOWN refers to the result after values of P078 and P079 are
multiplied.