English / Page 34
8. Connection and initial operation of the accessories
Connection plan:
Control elements S2 and S4 stop a running operator:
Following functions are available at connecting terminal X2c:
S0 (STOP):
Connection:
terminals 12 and 13 (remove short-circuit plug)
Contact category: opener
Connection mode:several contacts have to be connected
in series
!
S1 (IMPULSE):
Connection:
terminals 20 and 21
Contact category: closer
Connection mode:several contacts have to be connected
parallelly
!
S2 (OPEN):
Connection:
terminals 16 and 15
Contact category: closer
Connection mode:several contacts have to be connected
parallelly
!
S4 (CLOSE):
Connection:
terminals 16 and 17
Contact category: closer
Connection mode:several contacts have to be connected
parallelly
!
Fig. 15: Wiring diagram
Fig. 16: Wiring diagram