Chapter 5 Parameters
|
VFD-B-P Series
Revision April 2009, SW V1.00
5-11
Parameter Explanation
Settings
Factory
Setting
Customer
05-30
Time Duration of
14th Step Speed
00 to 65500 sec or 00 to 6550.0 sec
00
05-31
Time Duration of
15th Step Speed
00 to 65500 sec or 00 to 6550.0 sec
00
00: 1 sec
05-32 Time
Unit
Settings
01: 0.1 sec
00
05-33
The Amplitude of
Wobble Vibration
0.00~400.00 Hz
0.00
05-34
Wobble Skip
Frequency
0.00~400.00 Hz
0.00
Group 6 Protection Parameters
Parameter Explanation
Settings
Factory
Setting
Customer
460V series: 660.0V to 820.0V
780.0V
06-00
Over-Voltage Stall
Prevention
00: Disable over-voltage stall prevention
V/f control: 20 to 150%
120
06-01
Over-Current Stall
Prevention during
Accel
Vector control: 20 to 250%
170
V/f control: 20 to 150%
120
06-02
Over-Current Stall
Prevention during
Operation
Vector control: 20 to 250%
170
00: Disabled
01: Enabled during constant speed operation.
After the over-torque is detected, keep
running until OL2 occurs.
02: Enabled during constant speed operation.
After the over-torque is detected, stop
running.
03: Enabled during accel. After the over-
torque is detected, keep running until OL2
occurs.
06-03
Over-Torque
Detection Mode
(OL2)
04: Enabled during accel. After the over-
torque is detected, stop running.
00
V/f control: 30 to 150%
110
06-04
Over-Torque
Detection Level
Vector control: 10 to 200%
150
06-05
Over-Torque
Detection Time
0.1 to 60.0 sec
0.1
00: Standard motor (self cooled by fan)
01: Special motor (forced external cooling)
06-06
Electronic Thermal
Overload Relay
Selection
02: Disabled
02
06-07
Electronic Thermal
Characteristic
30 to 600 sec
60
00: No fault
01: Over current (oc)
06-08 Present
Fault
Record
02: Over voltage (ov)
00
Содержание VFD-B Series
Страница 1: ...PLC1 ir...
Страница 2: ......
Страница 3: ......
Страница 11: ......
Страница 61: ...Chapter 3 Start Up VFD B P Series 3 4 Revision April 2009 SW V1 00 This page intentionally left blank...
Страница 171: ...Chapter 5 Parameters VFD B P Series 5 106 Revision April 2009 SW V1 00 This page intentionally left blank...
Страница 189: ...Chapter 8 Maintenance and Inspections VFD B P Series 8 6 Revision April 2009 SW V1 00 This page intentionally left blank...
Страница 206: ...Appendix B Accessories VFD B P Series Revision April 2009 SW V1 00 B 15 Order P N 08TDT1W4C4 Order P N 50TDS4W4C...
Страница 207: ...Appendix B Accessories VFD B P Series B 16 Revision April 2009 SW V1 00 Order P N 100TDS84C Order P N 150TDS84C...
Страница 224: ......
Страница 229: ...Appendix B Accessories VFD B P Series B 40 Revision April 2009 SW V1 00 This page intentionally left blank...