Chapter 5 Parameters
|
VFD-B-P Series
5-78
Revision April 2009, SW V1.00
0
08-08
08-09
08-10
08-11
08-12
08-13
setting frequency
in
te
rn
a
l f
req
ue
ncy
c
o
mm
and
08 - 14
Auto Restart After Fault
Unit: 1
Settings
00 to 10
Factory Setting: 00
00
Disable
08 - 21
Auto Reset Time at Restart after Fault
Unit: 1
Settings
00 to 60000 sec
Factory Setting: 600
Only after an over-current OC or over-voltage OV fault occurs, the AC motor drive can be
reset/restarted automatically up to 10 times.
Setting this parameter to 00 will disable the reset/restart operation after any fault has occurred.
When enabled, the AC motor drive will restart with speed search, which starts at the frequency
before the fault.
This parameter should be used in conjunction with Pr.08-14.
For example: If Pr.08-14 is set to 10 and Pr.08-21 is set to 600s (10 min), and if there is no
fault for over 600 seconds from the restart for the previous fault, the Auto Reset Time for
restart after fault will be reset to 10.
08 - 15
Automatic Energy-saving
Factory Setting: 00
Settings
00
Energy-saving operation disabled
01
Energy-saving operation enabled
When automatic energy-saving function is enabled, it will operate with full voltage during
acceleration/deceleration. For the constant speed, it will give the best voltage which is auto
calculated by the load power to load.
Содержание VFD-B Series
Страница 1: ...PLC1 ir...
Страница 2: ......
Страница 3: ......
Страница 11: ......
Страница 61: ...Chapter 3 Start Up VFD B P Series 3 4 Revision April 2009 SW V1 00 This page intentionally left blank...
Страница 171: ...Chapter 5 Parameters VFD B P Series 5 106 Revision April 2009 SW V1 00 This page intentionally left blank...
Страница 189: ...Chapter 8 Maintenance and Inspections VFD B P Series 8 6 Revision April 2009 SW V1 00 This page intentionally left blank...
Страница 206: ...Appendix B Accessories VFD B P Series Revision April 2009 SW V1 00 B 15 Order P N 08TDT1W4C4 Order P N 50TDS4W4C...
Страница 207: ...Appendix B Accessories VFD B P Series B 16 Revision April 2009 SW V1 00 Order P N 100TDS84C Order P N 150TDS84C...
Страница 224: ......
Страница 229: ...Appendix B Accessories VFD B P Series B 40 Revision April 2009 SW V1 00 This page intentionally left blank...