Chapter 5 Parameters
|
VFD-B-P Series
Revision April 2009, SW V1.00
5-67
06 - 03
Over-Torque Detection Mode (OL2)
Factory Setting: 00
Settings
00
Over-Torque detection disabled.
01
Over-Torque detection enabled during constant speed operation.
After over-torque is detected, keep running until OL2 occurs.
02
Over-Torque detection enabled during constant speed operation.
After over-torque is detected, stop running.
03
Over-Torque detection enabled during acceleration. After over-
torque is detected, keep running until OL2 occurs.
04
Over-Torque detection enabled during acceleration. After over-
torque is detected, stop running.
This parameter determines the operation mode of the drive after the over-torque (OL2) is
detected via the following method: if the output current exceeds the over-torque detection level
(Pr.06-04) longer than the setting of Pr.06-05 Over-Torque Detection Time, the warning
message “OL2” is displayed. If a Multi-Functional Output Terminal is set to over-torque
detection (Pr.03-00~03-03=04), the output is on. Please refer to Pr.03-00~03-03 for details.
06 - 04
Over-Torque Detection Level (OL2)
Unit: 1
V/f Control
Settings
30 to 150%
Factory Setting: 110
Vector Control
Settings
10 to 200%
Factory Setting: 150
The control mode is set by Pr.00-09.
06 - 05
Over-Torque Detection Time (OL2)
Unit: 0.1
Settings
0.1 to 60.0 sec
Factory Setting: 0.1
This parameter sets the time for how long over-torque must be detected before “OL2” is
displayed.
06 - 06
Electronic Thermal Overload Relay Selection (OL1)
Factory Setting: 02
Settings
00
Operate with a Standard Motor (self-cooled by fan)
01
Operate with a Special Motor (forced external cooling)
02
Operation
disabled
This function is used to protect the motor from overloading or overheating.
06 - 07
Electronic Thermal Characteristic
Unit: 1
Settings
30 to 600 sec
Factory Setting: 60
Содержание VFD-B Series
Страница 1: ...PLC1 ir...
Страница 2: ......
Страница 3: ......
Страница 11: ......
Страница 61: ...Chapter 3 Start Up VFD B P Series 3 4 Revision April 2009 SW V1 00 This page intentionally left blank...
Страница 171: ...Chapter 5 Parameters VFD B P Series 5 106 Revision April 2009 SW V1 00 This page intentionally left blank...
Страница 189: ...Chapter 8 Maintenance and Inspections VFD B P Series 8 6 Revision April 2009 SW V1 00 This page intentionally left blank...
Страница 206: ...Appendix B Accessories VFD B P Series Revision April 2009 SW V1 00 B 15 Order P N 08TDT1W4C4 Order P N 50TDS4W4C...
Страница 207: ...Appendix B Accessories VFD B P Series B 16 Revision April 2009 SW V1 00 Order P N 100TDS84C Order P N 150TDS84C...
Страница 224: ......
Страница 229: ...Appendix B Accessories VFD B P Series B 40 Revision April 2009 SW V1 00 This page intentionally left blank...