21
ENGLISH
Operation and installation manual SOLIVIA 5.0 EU G3
The fi rst line shows the limits according the standard. The second line shows the actual measured
grid voltage and the test status, positive (pass) or negative (fail). Pressing the test is confi rmed
and the auto-test routine continue. If no is pressed, the result is shown for 1minute. After this
time, the result is confi rmed automatically.
The fi rst line shows the limits according the standard. The second line shows the actual measured
grid frequency and the test status, positive (pass) or negative (fail). Pressing the test is confi rmed
and the auto-test routine continue. If no is pressed, the result is shown for 1minute. After this
time, the result is confi rmed automatically.
The fi rst line shows the actual high frequency limit and detection time settings according to the
standards. Since the protection is not sensitive to the frequency variations less than 40 ms (two
line cycles of the grid voltage at nominal frequency of 50 Hz), the detection time has been set to
60 ms. Pressing the test starts. Test starts also automatically after 1 minute if no is pressed.
The fi rst line shows the actual low frequency limit and detection time settings according to the
standards. Since the protection is not sensitive to the frequency variations less than 40 ms (two line
cycles of the grid voltage at nominal frequency of 50 Hz), the detection time has been set to 60 ms.
Pressing the test starts. Test starts also automatically after 1 minute if no is pressed.
If has been pressed the display shows, for example:
The limit “L:” will increase till crossing the actual measured grid voltage “A:”. Reached this condition
the inverter display shows, for example:
L: 230 V 0.164 S
A: 230 V UV pass
If the test is confi rmed, the inverter performs the HFT test, high frequency test, which verify the high
frequency protection. The display shows:
L: 50.30 Hz < 0.06 S
Start HFT test?
L: 50.30 Hz HFT
A: 49.99 Hz RUN
The limit “L:” will decrease till crossing the actual measured grid frequency “A:”. Reached this con-
dition the inverter display shows, for example:
L: 49.99 Hz 0.044 S
A: 49.99 Hz HF pass
If the test is confi rmed, the inverter performs the LFT test, low frequency test, which verify the low
frequency protection. The display shows:
L: 49.70 Hz < 0.06 S
Start LFT test?
Содержание SOLIVIA 5.0
Страница 1: ...Operation and installation manual for SOLIVIA 5 0 EU G3 5 0 EU...
Страница 2: ......
Страница 4: ...2 Operation and installation manual SOLIVIA 5 0 EU G3...
Страница 40: ...38 Bedienungsanleitung SOLIVIA 5 0 EU G3 Bedienungsanleitung SOLIVIA 5 0 EU G3...
Страница 42: ...40 Bedienungsanleitung SOLIVIA 5 0 EU G3 Bedienungsanleitung SOLIVIA 5 0 EU G3...
Страница 78: ...76 Manuale di istruzioni SOLIVIA 5 0 EU G3...
Страница 80: ...78 Manuale di istruzioni SOLIVIA 5 0 EU G3...
Страница 192: ...190 Manual de instru es SOLIVIA 5 0 EU G3...
Страница 194: ...192 Manual de instru es SOLIVIA 5 0 EU G3...
Страница 230: ...228 N vod k obsluze SOLIVIA 5 0 EU G3...
Страница 232: ...230 N vod k obsluze SOLIVIA 5 0 EU G3...
Страница 268: ...266 N vod na prev dzku a in tal ciu SOLIVIA 5 0 EU G3 N vod na prev dzku a in tal ciu SOLIVIA 5 0 EU G3...
Страница 270: ...268 N vod na prev dzku a in tal ciu SOLIVIA 5 0 EU G3 N vod na prev dzku a in tal ciu SOLIVIA 5 0 EU G3...
Страница 306: ...304 Handleiding SOLIVIA 5 0 EU G3 Handleiding SOLIVIA 5 0 EU G3...
Страница 308: ...306 Handleiding SOLIVIA 5 0 EU G3 Handleiding SOLIVIA 5 0 EU G3...
Страница 344: ...342 SOLIVIA 5 0 EU G3...
Страница 345: ...343 SOLIVIA 5 0 EU G3 www solar inverter com Copyright Delta Energy Systems Germany GmbH Delta Energy Systems...
Страница 346: ...344 SOLIVIA 5 0 EU G3...
Страница 351: ...349 SOLIVIA 5 0 EU G3 4 3 1 2 3 RS485 EIA485 4 5 3 1 2 4 3 5...
Страница 359: ...357 SOLIVIA 5 0 EU G3 6 9 Solar Inverter MPP Booster DC Bus DC DC DC DC A B C D AC...
Страница 376: ...374 SOLIVIA 5 0 EU G3 10 10 1 400 230 V VNB Z 1 Z 2 1 2 400 230 V 4 6 kVA 400 230 V VNB Z 1 Z 2 1 2 400 230 V 4 6 kVA...
Страница 377: ...375 SOLIVIA 5 0 EU G3 DC DC 3 3 Z 3 Z 3 3 3 B 32 A Solivia 5 0 DC B 32 A DC B 32 A kWh kWh Solivia 5 0 Solivia 5 0 10 2...
Страница 378: ...376 SOLIVIA 5 0 EU G3 DC 1 2 3 L1 N PE L2 N PE L3 N PE L1 N n PE L2 L3 Solivia 5 0...
Страница 380: ...378 SOLIVIA 5 0 EU G3 Volta Alessandro Volta RJ45 RJ Registered Jack RS485 EIA485 TAB 2000 TAB 2000 2000 VDE VDEW...
Страница 381: ...379 SOLIVIA 5 0 EU G3 12 https guarantee solar inverter com SOLIVIA 5 10 5...
Страница 382: ...380 Operation and installation manual SOLIVIA 5 0 EU G3 13 Certificates...
Страница 383: ...381 Operation and installation manual SOLIVIA 5 0 EU G3...
Страница 390: ...388 Operation and installation manual SOLIVIA 5 0 EU G3 Notes...
Страница 391: ......