Chapter 7 Troubleshooting
No. Alarm Information
Possible cause
Elimination method
28
+XPLGL¿HU
1. The humidifying water has
a too high conductivity.
2. The humidifying water has
a too low conductivity.
3. The humidifying inlet valve
is abnormal.
4. The humidifying drain
valve is abnormal.
5. The humidifying cylinder
abnormal.
Inspect the humidifying cylinder.
29
Heater # Failed
1. The # heater connection is
incorrect.
2. The re-heating protector is
tripped.
1. Make sure the # heater
connection is correct.
2. Make sure the fans run normally.
30
Leak Wire Open
Leakage detector wire is not
properly connected
Check if the leakage detector is
loosened or disconnected or in poor
contact.
NOTE:
,IWKHDODUPVWLOOH[LVWVDIWHUWKHDERYHSRVVLEOHFDXVHVDUHHOLPLQDWHGSOHDVHFRQWDFW
your dealer or customer service.