35
Chapter 5 Operation
:
:
:
Auto Recover
Intelligent
Leak.Cut-Off
ON
ON
OFF
y
Forced operation
When the force mode is enabled, the fans will run at full speed and the two-way ball valve
will fully open, which is generally used for performance testing or at a high heat load. If the
STANDBY
LQGLFDWRURQWKHFRQWUROSDQHOÀDVKHVWKHXQLWLVLQWKHIRUFHPRGH
y
Min Flow T
When the return air temperature is lower than this value, the fans will run at the minimum
speed to save energy and the default is
25°C
.
y
Max Flow T
:KHQWKHUHWXUQDLUWHPSHUDWXUHLVKLJKHUWKDQWKLVYDOXHWKHIDQVZLOOUXQDWWKHPD[LPXP
speed to save energy and the default is
40°C
.
y
Fan Step
,WLVXVHGWRVHWWKHIDQVSHHGUDQJHaLQWKHDXWRPDWLFPRGH7KHGHIDXOWLV
0
and the
cooling unit will adjust the fan speed according to your setup.
y
Auto Recover
:KHQWKLVIXQFWLRQLVHQDEOHGDQGWKHV\VWHPLVLQWKHDXWRPDWLFPRGHEHIRUHSRZHURႇDW
a restart, the unit will directly return to the automatic mode.
y
Intelligent
Display if the intelligent temperature control is enabled. This option only displays the status.
You cannot change the setting. For change of setting, refer to
5.6.4 Setting of automatic
control mode
.
y
/HDN&XW2ႇ
Set if the unit will stop when the water leakage detector detects any leakage so as to
SUHYHQWOHDNDJHH[SDQVLRQ