Chapter 7 Troubleshooting
No. Alarm Information
Possible cause
Elimination method
4
Leak Active
Leakage is detected. Remove
the surplus water and
inspect the water level of the
condensed water pan.
Inspect if the drain function is normal
DQGFRQ¿UPWKDWWKHFRQGHQVHG
water pipe has no bending, damage
or blockage. If the upper piping is
DGRSWHGSOHDVHFRQ¿UPWKDWWKH
vertical elevation is no greater than
5 meters.
5
Fire Active
Fire detection is triggered.
Inspect the environment and
eliminate the abnormality.
6
Smoke Active
Smoke detection is triggered.
Inspect the environment and
eliminate the abnormality.
7
Comm Abnormal
The CAN-Link port wiring
is wrong or the unit ID is
repeated.
Inspect the CAN-Link port wiring
DQGFRQ¿UPWKDWWKHFRROLQJ
units connected in series have
independent and non-repeated IDs.
8
Return/Supply
Sensor
The air return/supply sensor is
abnormal or in bad contact.
Inspect the function of the air return/
VXSSO\VHQVRUDQGFRQ¿UPWKHZLULQJ
is stable.
9
Remote sensor # is
abnormal
Remote sensor # is abnormal
or in bad contact
Inspect the function of the sensor #
DQGFRQ¿UPWKHZLULQJLVVWDEOH
10
Abnormal chilled
water inlet sensor
The chilled water inlet sensor
is abnormal or in bad contact.
Inspect the function of the chilled
ZDWHULQOHWVHQVRUDQGFRQ¿UPWKH
wiring is stable.
11
Abnormal chilled
water outlet sensor
The chilled water outlet
sensor is abnormal or in bad
contact.
Inspect the function of the chilled
ZDWHURXWOHWVHQVRUDQGFRQ¿UPWKH
wiring is stable.
12
Flow Meter
7KHÀRZPHWHULVDEQRUPDORU
in bad contact.
,QVSHFWWKHIXQFWLRQRIWKHÀRZPHWHU
DQGFRQ¿UPWKHZLULQJLVVWDEOH
13
Fan number # failed
The # fan is abnormal or in
bad contact.
Inspect if the # fan is blocked or
DEQRUPDODQGFRQ¿UPWKHFRQQHFWLRQ
wire is correctly connected.
14
Chilled water ball
valve is abnormal
The three-way ball valve is
abnormal.
Inspect if the three-way ball valve is
in bad contact or faulty.