InfraSuite RowCool Precision Cooling –
Chilled Water
3.2 Clearance zone
In order to facilitate maintenance, operation, and air circulation, please reserve a net space
around the equipment.
It is suggested to preserve 1200mm in the front aisle, 600mm in the rear aisle, and at least
PPDERYHWKHFDELQHWWRIDFLOLWDWHZLULQJDQGSLSLQJ7KHKHLJKWRIUDLVHGÀRRUVKRXOGQRW
be lower than 300mm.
Ceiling
Wall
Raised floor
Common floor
Above: 300 mm
Below: 300 mm
(Raised floor ~ common floor)
1200
mm
600
mm
Front
Rear
(Figure 3-1: Space reservation)
3.3 Handling
y
Handling Instructions
Before moving the equipment to the installation site, plan the route according to the
IROORZLQJLQVWUXFWLRQV
0DNH VXUH WKH SDVVDJH ÀRRU HOHYDWRU RU VORSH RQ WKH KDQGOLQJ URXWH FDQ EHDU WKH
ZHLJKWRIWKHHTXLSPHQWDQGKDQGOLQJGHYLFHDQGWKHUHLVDVXႈFLHQWQHWVSDFHWRDYRLG
collisions.
2. In the case of a slope on the handling route, its inclination must not be greater than 15
degrees so as to avoid toppling the cabinet.