D V P 0 2 T K - S / D V P 0 2 T U - S T e m p e r a t u r e C o n t r o l M o d u l e M a n u a l
2 - 1 2
_2
TU
CR#
TK CH1
Page1
Add. (Hex)
TK CH2
Page11
Add. (Hex)
Attribute
Name
Description
Default
#35
043
123
R/W
O
Default integral
coefficient
K0~K10000 (The unit is 0.01)
K0
#36
044
124
R/W
O
Max. value of
MV
K0~K1000 (The unit is 0.1%)
K1000
#37
045
125
R/W
O
Min value of.
MV
K0~K1000 (The unit is 0.1%)
K0
Symbols: O: Latched. X: Non-latched.
R: Able to read data by FROM instruction. W: Able to write data by TO instruction.
2.1.6
Program Control Setup Page
TU
CR#
TK CH1
Page2
Address
(
Hex
)
TK CH2
Page12
Address
(
Hex
)
Attribute
Name
Description
Default
#11
04B
12B
R/W
O
Pattern number to start
running
K0~K7
K0
#12
04C
12C
R/W
O
Step number to start
running
K0~K7
K0
#13
04D
12D
R/W
O
The Cycle index of the
Pattern number 0~7 to
repeat running
K0~K99 indicates the running
times of the Pattern has
reached 100
K9999: running continuously
K0
#14
04E
12E
R
X
Read the current running
pattern number
K0~K8 (8 indicates ending)
K0
#15
04F
12F
R
X
Read the current running
step number
K0~K7
K0
#16
050
130
R
X
Read the step running
time left
Unit (seconds)
K0
#17
051
131
R/W
O
Pattern0_set up for the
max. step number to run
K0~K7
K0
#18
052
132
R/W
O
Pattern1_ set up for the
max. step number to run
K0~K7
K0
#19
053
133
R/W
O
Pattern2_ set up for the
max. step number to run
K0~K7
K0
#20
054
134
R/W
O
Pattern3_ set up for the
max. step number to run
K0
#21
055
135
R/W
O
Pattern4_ set up for the
max. step number to run
K0
#22
056
136
R/W
O
Pattern5_ set up for the
max. step number to run
K0
#23
057
137
R/W
O
Pattern6_ set up for the
K0