C h a p t e r 2 C o n t r o l R e g i s t e r
2 - 7
2_
TU
CR#
TK CH1
Page0
Add. (Hex)
TK CH2
Page10
Add. (Hex)
Attribute
Name
Description
Default
K14: N
K15: B
K16: L
K17: U
K18: TXK
K19: C
K20: PL II
K21: Cu50
K22: Cu100
K23: Ni100
K24: Ni1000
K25: LGNi1000
K26: 0~10V (Quick AI)
K27: Ni120
K28
:
-100mV ~ 100mV
K29
:
4 ~ 20mA (Quick AI)
#12
00C
0EC
R/W
O
Unit of
temperature
K0:
O
C
K1:
O
F
K0
#13
00D
0ED
R/W
O
Offset
temperature
error
K-999 ~ K999
K0
#14
00E
0EE
R/W
O
Temperature
filter range
Temperature filter ranges from K10
to K10000.
When the value inputted is in the
range of
±
10 of the last inputted
value, the system will run the
filtering measurement. Hence, when
the noise interference is bigger, the
filter range should set to bigger too.
K10
#15
00F
0EF
R/W
O
Filtering factor
Ranging K0~K50.
Operational formula: value = (last
value*n + this measurement ) / (n+1)
When the set value is less, the PV
will be closer to this measurement.
When the set value is bigger, the
filtering factor will be bigger and the
PV will be similar.
K1
#16
010
0F0
R/W
O
Control type
K0: PID Auto
K1: PID Manual
K2: PID program control
K3: ON/OFF
(for DVP02TUR-S/DVP02TUN-S/
DVP02TKR-S/DVP02TKN-S)
K0
Содержание DVP02TK-S