background image

 

4

Thermocouple E type 

 

0 ~ 600

o

Thermocouple T type 

 

-200 ~ 400

o

Thermocouple J type 

 

-100 ~ 1200

o

Thermocouple K type 

 

-200 ~ 1300

o

Note 1 : An external 250

Ω

 precision resistor should be connected when the current input is selected as the input 

temperature sensor type.. 

Note 2 : 

  (Operation mode) must be set if user wish to specify decimal point position. Except for the 

thermocouple B, S, R type, the decimal point positions of all the other thermocouple type input sensors can 
be set. 

 

The default range of analog input is -999 ~ 9999. For example, when a 0~20mA analog input is selected as the 

input temperature sensor type, -999 indicates 0mA and 9999 indicates 20mA. If change the input range to 0 ~ 
2000, then 0 indicates 0mA and 2000 indicates 20mA. One display scale is equal to 0.01mA. 

 

6  

Operation

 

 

There are three modes of operation: operation, regulation and initial setting. When power is applied, controller 
gets into the operation mode. Press the 

 key to switch to regulation mode. If the 

 key is pressed for 

more than 3 seconds, controller will switch to the initial setting mode. Pressing the 

 key while in the 

regulation mode or initial setting mode, forces the controller to return to the operation mode.   
PV/SV: Sets the temperature set point and displays the temperature process value. Use 

  keys to set the 

temperature set point. 

Setting method: While in any function mode, press the 

  key to select the desired function and use the 

 

keys to change settings. Press 

  key to save the changes.   

 

 
The next flow chart shows how to switch for settings and internal functions: 

 

Regulation Mode

Operation Mode

Initial Setting Mode

Press       key less than 3 sec

Press       key

Press       key more than 3 sec

Press       key

 

Regulation Mode

 

Operation Mode

 

Initial Setting Mode

 

Auto-tuning

(Set in PID control and RUN mode)

Press

 

Use              key to

set temperature set point

Press

 

Set input type

Press

 

4 groups PID modes (n=0~3). When n=4,
PID control is auto regulated.

Press

 

Press

Control setting RUN or STOP

 

Set temperature unit

do not display when analog input

Press

 

PD control offset

setting

(When PID control is ON and Ti=0, 
 set the value of PdoF.

Press

 

Start pattern setting (PID

program control and         

Time setting.

Press

 

Set upper-limit of
temperature range

Press

 

Heating hystereisis setting

(Set in ON/OFF control mode)

Press

 

Decimal point position selection

(except for B, S, R type, all the
 other types can be set)

Press

 

Set lower-limit of

temperature range

Press

 

Cooling hystereisis setting

(Set in ON/OFF control mode)

Press

 

Upper-limit alarm 1

(This parameter is available only when 
  ALA1 function enables)

Press

Select control mode

(See "Pattern and set Editing 
selection" for detail)

Press

 

Содержание DT4848

Страница 1: ...http www delta com tw industrialautomation DELTA Temperature Controller DTB Series User Manual...

Страница 2: ...e correct polarity of terminals 6 Do not install and or use the controller in places subject to Dust or corrosive gases and liquid High humidity and high radiation Vibration and shock High voltage and...

Страница 3: ...de C Celsius F Fahrenheit Press this key to increase values displayed on the SV display Hold down this key to speed up the incremental action Mode key key O O O 3 Ordering Information DTB 1 2 3 4 5 6...

Страница 4: ...racter 7 segment LED display Process value PV Red color Set point SV Green color Thermocouple K J T E N R S B L U TXK 3 wire Platinum RTD Pt100 JPt100 Sensor Type Analog input 0 5V 0 10V 0 20 m A 4 20...

Страница 5: ...emperature set point and displays the temperature process value Use keys to set the temperature set point Setting method While in any function mode press the key to select the desired function and use...

Страница 6: ...m full close to full open Display when valve control is ON Press Display and adjust output value of 1st output group Display in PID control mode and manual RUN mode Press ASCII RTU communication forma...

Страница 7: ...Press to return pattern No editing mode Press to set actual step No Edit time of step No 7 of pattern No 0 unit is hh mm 7 Dual Loop Output Control Heating Cooling Control OFF PV Set point ON Heating...

Страница 8: ...initial setting mode The alarm output is activated whenever the process temperature value PV is getting higher or lower than the set point of alarm limit Set Value Alarm Type Alarm Output Operation 0...

Страница 9: ...t You can set current alarm range between 0 5A 30A display resolution is 0 1A and measure accuracy is 0 5A 10 EVENT Inputs Function 5 There are two optional event inputs contact inputs supported EVENT...

Страница 10: ...ay on SV display 12 PID Control One group can be selected from any one of 4 groups PID parameters P I D IOF for PID control After AT PID value and temperature setting will be stored in the selected on...

Страница 11: ...tents of the Temperature Sensor Type and Temperature Range for detail 1005H Control method 0 PID 1 ON OFF 2 manual tuning 3 PID grogram control 1006H Heating Cooling control selection 0 Heating 1 Cool...

Страница 12: ...102BH Read pushbutton status b0 Set b1 Select b2 Up b3 Down 0 is to push 102CH Setting lock status 0 Normal 1 All setting lock 11 Lock others than SV value 102DH CT read value Unit 0 1A 102FH Softwar...

Страница 13: ...0 0 02 0 0 6 0 0 02 0 mm in DTB4824 1 4 3 2 5 6 AC 100 240V 50 60 Hz 5VA Tc RTD OUT 1 DATA DATA RS 485 7 9 8 10 11 12 V OUT 2 ALM V IN L N DTB4848 65 0 min 2 56 45 0 1 77 45 0 1 77 60 0 min 2 36 0 6...

Страница 14: ...9 in 9 5 mm 0 37 in 80 0 mm 3 15 in 44 75 mm 1 76 in 45 0 mm 1 77 in 0 6 0 45 0 mm 1 77 in 0 6 0 0 02 0 0 02 0 DTB4896 DTB9696 48 0 mm 1 89 in 12 8 mm 0 50 in 79 2 mm 3 12 in 91 0 mm 3 58 in 95 7 mm 3...

Страница 15: ...B4848 4896 9696 Mounting Method 1 3 2 0 6 8 m m M a x 17 Error Acknowledge and Display Communication error code response description Error status 102EH 4750H PV read back 1000H 4700H Error status 0001...

Страница 16: ...AN TEL 886 3 362 6301 FAX 886 3 362 7267 NORTH SOUTH AMERICA DELTA PRODUCTS CORPORATION Sales Office P O BOX 12173 5101 DAVIS DRIVE RTP NC 27709 U S A TEL 1 919 767 3813 FAX 1 919 767 3969 EUROPE DELT...

Отзывы: