4
Thermocouple E type
3
0 ~ 600
o
C
Thermocouple T type
2
-200 ~ 400
o
C
Thermocouple J type
1
-100 ~ 1200
o
C
Thermocouple K type
0
-200 ~ 1300
o
C
Note 1 : An external 250
Ω
precision resistor should be connected when the current input is selected as the input
temperature sensor type..
Note 2 :
(Operation mode) must be set if user wish to specify decimal point position. Except for the
thermocouple B, S, R type, the decimal point positions of all the other thermocouple type input sensors can
be set.
The default range of analog input is -999 ~ 9999. For example, when a 0~20mA analog input is selected as the
input temperature sensor type, -999 indicates 0mA and 9999 indicates 20mA. If change the input range to 0 ~
2000, then 0 indicates 0mA and 2000 indicates 20mA. One display scale is equal to 0.01mA.
6
Operation
There are three modes of operation: operation, regulation and initial setting. When power is applied, controller
gets into the operation mode. Press the
key to switch to regulation mode. If the
key is pressed for
more than 3 seconds, controller will switch to the initial setting mode. Pressing the
key while in the
regulation mode or initial setting mode, forces the controller to return to the operation mode.
PV/SV: Sets the temperature set point and displays the temperature process value. Use
keys to set the
temperature set point.
Setting method: While in any function mode, press the
key to select the desired function and use the
keys to change settings. Press
key to save the changes.
The next flow chart shows how to switch for settings and internal functions:
Regulation Mode
Operation Mode
Initial Setting Mode
Press key less than 3 sec
Press key
Press key more than 3 sec
Press key
Regulation Mode
Operation Mode
Initial Setting Mode
Auto-tuning
(Set in PID control and RUN mode)
Press
Use key to
set temperature set point
Press
Set input type
Press
4 groups PID modes (n=0~3). When n=4,
PID control is auto regulated.
Press
Press
Control setting RUN or STOP
Set temperature unit
do not display when analog input
Press
PD control offset
setting
(When PID control is ON and Ti=0,
set the value of PdoF.
Press
Start pattern setting (PID
program control and
Time setting.
Press
Set upper-limit of
temperature range
Press
Heating hystereisis setting
(Set in ON/OFF control mode)
Press
Decimal point position selection
(except for B, S, R type, all the
other types can be set)
Press
Set lower-limit of
temperature range
Press
Cooling hystereisis setting
(Set in ON/OFF control mode)
Press
Upper-limit alarm 1
(This parameter is available only when
ALA1 function enables)
Press
Select control mode
(See "Pattern and set Editing
selection" for detail)
Press