background image

 

8

Deviation upper-limit with standby sequence: 
This alarm output operates when PV value reaches set point (SV value) and the 
reached value is higher than the setting value SV+(AL-H).   

SV+(AL-H)

ON

OFF

SV

10  Deviation lower-limit with standby sequence:   

This alarm output operates when PV value reaches the set point (SV value) and the 
reached value is lower than the setting value SV-(AL-L). 

SV-(AL-L)

ON

OFF

SV

11  Hysteresis upper-limit alarm output: 

This alarm output operates if PV value is higher than the setting value SV+(AL-H). 
This alarm output is OFF when PV value is lower than the setting value SV+(AL-L).

 

ON

OFF

AL-L AL-H

12  Hysteresis lower-limit alarm output:   

This alarm output operates if PV value is lower than the setting value SV-(AL-H). 
This alarm output is OFF when PV value is higher than the setting value SV-(AL-L). 

ON

OFF

AL-H AL-L

13  CT alarm output: 

This alarm operates when the current measured by transformer (CT) is lower than 
AL-L or higher than AL-H (This alarm output is available only for the controller with 
current transformer). 

ON

OFF

AL-L

SV

AL-H

14  When program control is end status, alarm output is ON. 

 

15  When RAMP UP status happens to PID program control, alarm output is ON. 

 

16  When RAMP DOWN status happens to PID program control, alarm output is ON. 

 

17  When SOAK status happens to PID program control, alarm output is ON. 

 

18  When RUN status happens to PID program control, alarm output is ON. 

 

Note: AL-H and AL-L include AL1H, AL2H, AL3H and AL1L, AL2L, AL3L 

9   

Current Transformer (CT) Function

 

 

The Current Transformer (CT) function is used with the alarm output. When using a current transformer (CT) with 

the controller, change the corresponding alarm output mode to mode 13 (alarm output set value is 13), then turn 

to operation mode and set the current lower-limit and current upper-limit. You can set current alarm range 

between 0.5A ~ 30A, display resolution is 0.1A and measure accuracy is +/- 0.5A. 

 

10   

EVENT Inputs Function

 


 

There are two optional event inputs (contact inputs) supported (EVENT1and EVENT2) in DTB series. 

EVENT1: 

RUN/STOP operation can be executed by RUN/STOP parameters (Operation Mode) or via the 

communication. User also can control RUN/STOP operation by EVENT 1 in DTB series. The control 

output is ON if the circuit of EVENT 1 is open when the controller is operating. Otherwise, the 

controller will stop output if the circuit of EVENT 1 is short or when the system parameter of the 

controller is set to STOP mode. 

EVENT2: 

DTB series allows user can switch two temperature setting value by changing the status (open/short) of 

EVENT 2. Each temperature setting value has independent control parameters. 

 

 

11   

PID Program Control (Ramp/Soak Program Control)

 

 

Description of Function and Parameters Setting: 

PID program control by 8 patterns (Pattern No. 0~7) is supported in DTB series. Each pattern contains 8 steps 

(step No. 0 ~ 7), one Link Pattern parameter, one Cycle parameter and one Actual Step parameter. 

 

Start Pattern

 

  is in operation mode and it is used to set the Start Pattern of PID program control (This 

parameter appear in 

 mode only). 

 

Steps :

 Include set point X and execution time T, these two parameters setting. The set point (SV) should reach 

temperature X after the period of execution time T. If the set point is the same as the result of the previous 
setting, then it is called Soak program control. If not, then it is called Ramp program control. Therefore, 
PID program control is also called Ramp/Soak program control. The default of step No. 0 in this controller 
is Soak program control. The controller will control the temperature (PV) to reach the set point X and then 
keep the temperature at set point X. The period of execution time is time T which provided by step No. 0. 

 

Link Pattern Parameter : 

For example, when set 

  to 2, it indicates that pattern No. 2 will execute next after 

Содержание DT4848

Страница 1: ...http www delta com tw industrialautomation DELTA Temperature Controller DTB Series User Manual...

Страница 2: ...e correct polarity of terminals 6 Do not install and or use the controller in places subject to Dust or corrosive gases and liquid High humidity and high radiation Vibration and shock High voltage and...

Страница 3: ...de C Celsius F Fahrenheit Press this key to increase values displayed on the SV display Hold down this key to speed up the incremental action Mode key key O O O 3 Ordering Information DTB 1 2 3 4 5 6...

Страница 4: ...racter 7 segment LED display Process value PV Red color Set point SV Green color Thermocouple K J T E N R S B L U TXK 3 wire Platinum RTD Pt100 JPt100 Sensor Type Analog input 0 5V 0 10V 0 20 m A 4 20...

Страница 5: ...emperature set point and displays the temperature process value Use keys to set the temperature set point Setting method While in any function mode press the key to select the desired function and use...

Страница 6: ...m full close to full open Display when valve control is ON Press Display and adjust output value of 1st output group Display in PID control mode and manual RUN mode Press ASCII RTU communication forma...

Страница 7: ...Press to return pattern No editing mode Press to set actual step No Edit time of step No 7 of pattern No 0 unit is hh mm 7 Dual Loop Output Control Heating Cooling Control OFF PV Set point ON Heating...

Страница 8: ...initial setting mode The alarm output is activated whenever the process temperature value PV is getting higher or lower than the set point of alarm limit Set Value Alarm Type Alarm Output Operation 0...

Страница 9: ...t You can set current alarm range between 0 5A 30A display resolution is 0 1A and measure accuracy is 0 5A 10 EVENT Inputs Function 5 There are two optional event inputs contact inputs supported EVENT...

Страница 10: ...ay on SV display 12 PID Control One group can be selected from any one of 4 groups PID parameters P I D IOF for PID control After AT PID value and temperature setting will be stored in the selected on...

Страница 11: ...tents of the Temperature Sensor Type and Temperature Range for detail 1005H Control method 0 PID 1 ON OFF 2 manual tuning 3 PID grogram control 1006H Heating Cooling control selection 0 Heating 1 Cool...

Страница 12: ...102BH Read pushbutton status b0 Set b1 Select b2 Up b3 Down 0 is to push 102CH Setting lock status 0 Normal 1 All setting lock 11 Lock others than SV value 102DH CT read value Unit 0 1A 102FH Softwar...

Страница 13: ...0 0 02 0 0 6 0 0 02 0 mm in DTB4824 1 4 3 2 5 6 AC 100 240V 50 60 Hz 5VA Tc RTD OUT 1 DATA DATA RS 485 7 9 8 10 11 12 V OUT 2 ALM V IN L N DTB4848 65 0 min 2 56 45 0 1 77 45 0 1 77 60 0 min 2 36 0 6...

Страница 14: ...9 in 9 5 mm 0 37 in 80 0 mm 3 15 in 44 75 mm 1 76 in 45 0 mm 1 77 in 0 6 0 45 0 mm 1 77 in 0 6 0 0 02 0 0 02 0 DTB4896 DTB9696 48 0 mm 1 89 in 12 8 mm 0 50 in 79 2 mm 3 12 in 91 0 mm 3 58 in 95 7 mm 3...

Страница 15: ...B4848 4896 9696 Mounting Method 1 3 2 0 6 8 m m M a x 17 Error Acknowledge and Display Communication error code response description Error status 102EH 4750H PV read back 1000H 4700H Error status 0001...

Страница 16: ...AN TEL 886 3 362 6301 FAX 886 3 362 7267 NORTH SOUTH AMERICA DELTA PRODUCTS CORPORATION Sales Office P O BOX 12173 5101 DAVIS DRIVE RTP NC 27709 U S A TEL 1 919 767 3813 FAX 1 919 767 3969 EUROPE DELT...

Отзывы: