![Delta AH10EN-5A Series Скачать руководство пользователя страница 66](http://html1.mh-extra.com/html/delta/ah10en-5a-series/ah10en-5a-series_operation-manual_2471620066.webp)
E t her Net / I P O per at i on M anual
5 - 6
_5
IP1
16#C0A8
IP address: 192.168.1.10
IP2
16#010A
Mode
16#01
Create a CIP connection and close the
connection after the transmission is
done.
SerCode
16#10
Write a single one Attribute
ClassId
16#9D
Class ID = 9D
InstId
16#02
Instance ID = 2
AttrId
16#01
Attribute ID =1
Size
16#02
Target parameter type: 2Bytes
Data
16#01
Parameter value: 16#01
When the function blocks are executed successfully, the output parameters will be stated as below.
Output
Parameter
Settings
Description
Don
ON (16#01)
Complete
Error
No output
No error
ErrCode
16#00
No error
Value
No output
No output
When the function blocks are not executed successfully, the output parameters will be stated as below.
Output
Parameter
Settings
Description
Don
No output
No output
Error
ON (16#01)
Error
ErrCode
16#0E
Cannot write the attribute
Value
No output
No output
The Error bit is On and the ErrCode=16#1401 (The I/O module appears to have an read/write error.)
Don and Value are shown with no output. No other FBs are used.
Содержание AH10EN-5A Series
Страница 16: ...EtherNet IP Operation Manual 2 6 _2 MEMO ...
Страница 24: ...EtherNet IP Operation Manual 3 8 _3 MEMO ...
Страница 46: ...EtherNet IP Operation Manual 4 22 _4 c EDS Parameter Tab this is not supported on the AH10EN 5A series ...
Страница 72: ...EtherNet IP Operation Manual 5 12 _5 MEMO ...
Страница 78: ...EtherNet IP Operation Manual 6 6 _6 MEMO ...
Страница 92: ...EtherNet IP Operation Manual 7 14 _7 MEMO ...