Chapt er 5 P r o gr am m i ng
5 - 5
5_
IP2
16#010A
Mode
16#00
UCMM
SerCode
16#0E
Read/write a single one attribute service
code
ClassId
1
Class ID = 1
InstId
1
Instance ID = 1
AttrId
1
Attribute ID =1
Size
No need to set up
No need to set up
Data
No need to set up
No need to set up
When the function blocks are executed successfully, the output parameters will be stated as below.
Output
Parameter
Settings
Description
Don
ON (16#01)
Complete
Error
No output
No error
ErrCode
16#00
No error
Value
16#031F
Delta’s manufacturers code
When the function blocks are not executed successfully, the output parameters will be stated as below.
Output
Parameter
Settings
Description
Don
No output
No output
Error
ON (16#01)
Error
ErrCode
16#07
Connection lost
Value
No output
No output
Example 2: Create a CIP connection and change the parameter value of the node 192.168.1.10 to 16#01. Close the
connection after the transmission is done.
Parameters: ClassId= 16#9D, InstId= 2, AttrId= 1
The parameters in the function blocks are as below:
Input
Parameter
Settings
Description
BID
16#01
Backplane 1
SID
16#01
Slot 1
PID
16#01
Содержание AH10EN-5A Series
Страница 16: ...EtherNet IP Operation Manual 2 6 _2 MEMO ...
Страница 24: ...EtherNet IP Operation Manual 3 8 _3 MEMO ...
Страница 46: ...EtherNet IP Operation Manual 4 22 _4 c EDS Parameter Tab this is not supported on the AH10EN 5A series ...
Страница 72: ...EtherNet IP Operation Manual 5 12 _5 MEMO ...
Страница 78: ...EtherNet IP Operation Manual 6 6 _6 MEMO ...
Страница 92: ...EtherNet IP Operation Manual 7 14 _7 MEMO ...