Calculating CIP Connection
Users can refer to the EIP Builder data exchange page (see below) to find out the number of CIP and TCP
connections. The method for calculating the number of CIP connection is also listed below. .
Series
Model
Method to Calculate CIP Connection
Adapter
Scanner
AH
AHRTU-ETHN-5A
Limited to AHCPU and third-party host
1) RTU + DIO uses 1 connection
2) Each AIO or NIO module uses 1 connection
Do not support
AH10EN-5A
Each data exchange group uses 1 connection
AHCPU5x1-EN
1) Each data exchange group uses 1 connection
2) Execute instruction API2208 EIPRW uses 1 connection
AHCPU560-EN2
AS
AS-FEN02
1) If using AS series or a third-party as the host
CPU, RTU + DIO + AIO use 1 connection
2) If using AH series as the host CPU, RTU +
DIO use 1 connection, each AIO module
uses 1 connection
Do not support
AS300
1) Each data exchange group uses 1 connection
2) Execute instruction API2208 EIPRW uses 1 connection
AS200
DVP
DVPES2-E
Each data exchange group uses 1 connection
Do not support
DVP26SE
Each data exchange group uses 1 connection
Do not support
VFD
CMC-EIP01
Each VFD uses 1 connection
Do not support
CMM-EIP01
Each VFD uses 1 connection
Do not support
Содержание AH10EN-5A Series
Страница 16: ...EtherNet IP Operation Manual 2 6 _2 MEMO ...
Страница 24: ...EtherNet IP Operation Manual 3 8 _3 MEMO ...
Страница 46: ...EtherNet IP Operation Manual 4 22 _4 c EDS Parameter Tab this is not supported on the AH10EN 5A series ...
Страница 72: ...EtherNet IP Operation Manual 5 12 _5 MEMO ...
Страница 78: ...EtherNet IP Operation Manual 6 6 _6 MEMO ...
Страница 92: ...EtherNet IP Operation Manual 7 14 _7 MEMO ...