NOTE: 

DO NOT USE EXCESSIVE FORCE to close the inlet stop stem. We RECOMMEND that the flushometer be flushed while closing 

the inlet stop. The noise created by the water flow or the flow into the fixture will stop when the inlet water is shut off.

NOTE: 

Always use DELTA COMMERCIAL GENUINE PARTS to maintain the warranty.

EXCESSIVE NOISE:

1. 

PARTIALLY close the inlet stop.

2. 

Pressures OVER 75 PSI may lead to an increase in NOISE, water could SPLASH out of the fixture more easily and the LIFE of any 

plumbing valve may be SHORTENED.

3. 

INSTALL a Pressure Reducing Valve set at a lower pressure if actual pressure is over 75 PSI. While the TECK Flushometer will operate 

up to 125 PSI, the preferred operating range is between 35 to 65 PSI.

4. 

On flushometers that have been installed for a number of years, check the Renewable Seat (062007A, item #12) for wear and replace if 

necessary.

EXCESSIVE WATER FLOW RATE:

1. 

OPEN inlet stop ONE TURN and adjust Regulating Screw (061024A, item #8a) to the fixture requirement (except on -6, -19, -05, -42 

and -48 models which are fixed volume).

2. 

Operation of flushometer with inlet stop BELOW ONE TURN OPEN may cause EXCESSIVE NOISE. The lowest open setting for the 

inlet stop may vary dependent on the installation.

SHORTAGE OF WATER TO PROPERLY FLUSH BOWL:

1.  OPEN inlet stop fully.

2.  CHECK pipeline for size or obstruction, partially closed gate or other supply line valve, corroded or undersize water piping.

3.  CHECK water pressure.

4. 

Water flow rate is determined by BOTH the water pipe size AND the water pressure available.

5. 

A water closet flush valve requires a minimum water supply of 1” (or larger), depending on a number of different factors including water 

pressure (PSI) available, pipe size and length of pipe run, number of fixtures per washroom and per building, fixture type, fixture usage 

factor, elevation of valve above the water main, etc. We strongly recommend that pipe size calculations be done to insure proper water 

supply sizes. 

Flushometers DO NOT provide a water supply; they are merely automatically timed self-closing valves. The inlet supply piping is the water 

reservoir that must supply sufficient water volume in a short period of time (4 to 10 seconds) to properly flush and clear the fixture.

CONTINUOUS FLUSHING:

1. 

The Regulating Screw (061024A, item #8a) may be turned RIGHT (clockwise) TOO FAR. Adjust by slowly turning the Regulating Screw 

LEFT (counter-clockwise) (except -6, -19, -05, -42 and -48 models which are fixed volume).

2. 

If flush is still continous, close inlet stop, remove Regulating Screw (061024A, item #8a), CLEAN bypass slot in the Screw, REPLACE it 

in the valve and ADJUST slowly for proper flush (except -6, -42, -48, -19 and -05 models which are fixed volume).

3. 

Remove cast cap assembly (item #8b) and Diaphragm/Guide Assembly (061323A - WC item #10a or 061324A - UR, item #10b) and 

check for contaminants at renewable seat (item #12) and diaphragm and check for debris in the cap for blockage. Also CHECK that the 

Diaphragm/Guide slides easily in the Renewable Seat. 

VALVE WILL NOT FLUSH:

1.  When the valve has been taken apart for servicing and re-assembled and does NOT operate, check that the Cast Cap has been put on 

the body properly. The Regulating Screw (061024A, item #8a) should always be on the same side as the inlet stop.

2. 

When all lights operate as expected but valve will not flush, check that the solenoid makes a clicking sound. If no clicking sound is 

present, then replace with Cap Assembly (item #8b).

3. 

After a number of years, the valve will flush but shuts off immediately when activated. The Diaphragm (060079A-MMO, item #10c) is 

worn or split and needs replacing.

SLIGHT WATER LEAK INTO FIXTURE:

1. 

EXAMINE the seating surface of the Diaphragm (060079A-MMO item #10c) for imbedded sediment.

CLEANING INSTRUCTIONS

CLEAN the outside of the chrome plated flushometer with a damp cloth.

CAUTION:

 MOST Tub & Tile fixture cleaners contain ACIDS. DO NOT WIPE the cloth used to clean ceramic fixtures over the flushometer 

as it will remove the chrome plating and leave a discoloured surface

.

PROBLEM SOLVING & MAINTENANCE SUGGESTIONS

Содержание 160 T6 Series

Страница 1: ...d 213777 Rev A Electronic Concealed Flushvalve 160__T6__ __ __A series Write purchase model number here for future reference 6 13 14 24VAC 6 VDC Filter Screen Nut Fibre washer Rubber washer Slip Joint Nut Installation For valves manufactured after October 2014 11b 8b 11a 11c 9 8a 12 15 22 10b 10a 10c 3 2 22 23 16 5 18 17 6 19 20 4 26 7 21 25 1 24 ...

Страница 2: ...6 gal adjustable water closets see Table 1 9 060078A Screws for Cast Cap 4 pkg 10a 061323A Diaphragm Guide Assembly Complete W C see Table 1 10b 061324A Diaphragm Guide Assembly for Urinals See Table 1 10c 060079A MMO Diaphragm only 12 pkg 11a 060507A Poppet Pin Pack 3 pkg also see 11b See Table 1 11b 060508A Poppet Pin Pack 3 pkg 0 5L Valves only See Table 1 11c 062025A Washer 3 pkg required for ...

Страница 3: ...061341A 060508A 061324A 1 9L 0 5 gal 061342A 060507A UR Adjustable 1 9L 0 5 gal 061346A W C Fixed 4 2L 1 1 gal 061343A 060507A 062025A 061323A 4 8L 1 27 gal 061344A 6 0L 1 6 gal 061345A W C Adjustable 6 0L 1 6 gal 061169A NOTE Must use all noted components listed in Table 1 to ensure correct flush volumes Fixed models have epoxy in the adjustment screw WaterSense compliant when paired with a WaterS...

Страница 4: ...M VALVES The FIRST FLUSH should ELIMINATE all air from the TECK flushometer DO NOT ADJUST flushometer based on the results of the first flush TO PREVENT WATER HAMMER A capped pipe vertical AIR CHAMBER may be installed at the last flushometer and or at the back of an individual installation This assures SMOOTHER OPERATION of the valves and longer life for the working parts FLUSH VOLUME ADJUSTMENT 1...

Страница 5: ... are positioned correctly 4 Sensor Plate Models If Battery Operated 102 mm 4 box and 4 box extension is supplied Remove suitable knockout as per Fig 1A Attach box extension to front of the box Rough in box assembly for sensor location as per Fig 1D Note Solenoid extension cord supplied with the trim is 1 220 mm 48 long Securely attach box to wall structure Attach supplied plasterguard as per Fig 1...

Страница 6: ... Solid Lines All Items Shown by Dotted Lines Supplied by Others 76mm 3 to BOF 76mm 3 to BOF of sensor Centerline C L of sensor Centerline C L of sensor Centerline C L 165mm 6 5 222mm 8 75 to BOF of sensor of sensor of sensor 57mm 2 25 to BOF 4 1 2 square stainless steel plate box 4 x 4 14 square stainless steel plate frame 12 x 12 14 x 20 stainless steel plate frame 12 x 18 4 1 2 square stainless ...

Страница 7: ... the wall framing etc STEP 2 INSTALL SENSOR PLATE Sensor Extension Cord Fig 2 STEP 3 OPERATION MODE A sequence of red lights that strobe across the sensing lens window will signify that the valve is now in operation mode Once in operation mode if factory settings are preferred no further action is required and the valve installation is complete Factory pre set functions are Water closet sensing di...

Страница 8: ...ng distance for urinal 24 sensing distance for water closet Press override button until pulsating blue light is present The blue light indicates that the sensing distance has been adjusted to a position that is detecting you Water closet only Now stand back and ensure that the pulsating blue light disappears when you stand near the door of the water closet Ensure that the door is not being detecte...

Страница 9: ...e size calculations be done to insure proper water supply sizes Flushometers DO NOT provide a water supply they are merely automatically timed self closing valves The inlet supply piping is the water reservoir that must supply sufficient water volume in a short period of time 4 to 10 seconds to properly flush and clear the fixture CONTINUOUS FLUSHING 1 The Regulating Screw 061024A item 8a may be t...

Страница 10: ...ERIOD OR THE DURATION OF THIS WARRANTY WHICHEVER IS SHORTER Some states provinces do not allow limitations on how long an implied warranty or condition lasts so the above limitation may not apply to you Limitation of Special Incidental or Consequential Damages MASCO CANADA LIMITED SHALL NOT BE LIABLE FOR ANY SPECIAL INCIDENTAL OR CONSEQUENTIAL DAMAGES INCLUDING LABOR CHARGES TO REPAIR REPLACE INST...

Отзывы: