Configuring Output Devices
This section covers the following topics:
l
Main Steps for Configuring Output Devices
l
l
Configuring Load Controllers with Central Command Support
l
Configuring Radiator Valve Controllers
Main Steps for Configuring Output Devices
The initial steps for configuring an EnOcean output device are the same as for configuring an
EnOcean input device. For detailed instructions regarding steps 1 to 4, refer to the previous
section,
1. In enteliWEB, open the NP object corresponding to the network port that the O3 Hub or
CON-ENOC is connected to, and set the Protocol Type to EnOcean.
2. If you are using O3 Hubs, create a BV30s030 object for each hub (where s is the hub
address in the range 2 to 9) to enable its EnOcean radio, and command the object to On.
3. Create the network and device SV objects.
4. Associate a mapping file with each device SV object.
5. Create the BACnet objects needed for your application, either manually or using the
Database Creation tool.
6. Pair each EnOcean device to its device SV object. The EnOcean output device is put into
learn mode and a learn out packet is sent from the gateway to the device.
The remainder of this section will focus on
steps 5 and 6
.
Configuring Simple Relays
Simple relays provide basic on/off control and do not offer any feedback.
The mapping file should contain the following objects:
14
O3-DIN EnOcean Application Guide
Edition 1.0