Ethernet Communication Module DVPEN01-SL
DVP-PLC Application Manual
7
CR#
HW
LW
Attribute
Content
Explanation
#7 R
Status of E-Mail 1, 2
b0 ~ b7: Current status of E-Mail 2
b8 ~ b15: Current status of E-Mail 1
#8
R
Status of E-Mail 3, 4
b0 ~ b7: Current status of E-Mail 4
b8 ~ b15: Current status of E-Mail 3
#9 R/W
E-Mail 1 additional
message
Filled in by the user, and it will be send by E-mail.
#10 R/W
E-Mail 2 additional
message
Filled in by the user, and it will be send by E-mail.
#11 R/W
E-Mail 3 additional
message
Filled in by the user, and it will be send by E-mail.
#12 R/W
E-Mail 4 additional
message
Filled in by the user, and it will be send by E-mail.
#13
R/W
Data exchange trigger
Set up whether to send out data in data exchange mode
#14
R
Status of data exchange Displaying current status of data exchange.
#24 ~ #15
-
Reserved
#26 #25 R/W Destination
IP
Destination IP address for data exchange
#27 - Reserved
#28
R/W
Destination Slave ID
Destination Slave ID for data exchange
#48 ~ #29
R/W
Data transmission buffer Buffer for transmitted data in data exchange
#68 ~ #49
R
Data receiving buffer
Buffer for received data in data exchange
#69 R/W
DHCP/Static
IP
Selecting DHCP or Static IP
#71 #70
R/W
IP address
Setting up IP address
#73 #72
R/W
Subnet mask
Setting up subnet mask of DVPEN01-SL
#75 #74
R/W
Gateway
Setting up default gateway IP address
#76
R
IP status
Displaying current IP status
#80 ~ #77
-
Reserved
#81 R/W
Read address for data
exchange
Slave transmission buffer address for data exchange
#82 R/W
Read length for data
exchange
Number of registers for read data
#83 R/W
Received address for
data exchange
Buffer address for the receiving Master in data exchange
#84 R/W
Written-in address for
data exchange
Buffer address for the receiving Slave in data exchange
#85 R/W
Written-in length for data
exchange
Number of registers for data transmission
#86 R/W
Transmission address
for data exchange
Master transmission buffer address for data exchange
#110 ~ #87
-
Reserved
#111
R/W
8-bit processing mode
Setting up Modbus TCP Master control as 8-bit mode
#113 ~ #112
-
Reserved
#114
R/W
Modbus TCP time-out
Setting up Modbus TCP time-out (in ms)
#115
R/W
Modbus TCP trigger
Setting up whether to send out data in Modbus TCP mode
#116
R/W
Modbus
TCP
status Displaying current status of Modbus TCP mode
#118 #117 R/W
Modbus TCP
destination IP
Setting up destination IP address for Modbus TCP transaction
Содержание Ethernet Communication Module DVPEN01-SL
Страница 1: ...DVPEN01 SL Ethernet Communication Module Application Manual ...
Страница 2: ......
Страница 54: ...Ethernet Communication Module DVPEN01 SL DVP PLC Application Manual 52 MEMO ...