Use TO instruction to write the network setting parameters D0 ~ D7 into CR#69 ~ #75 in
DVPEN01-SL. DVPEN01-SL is the first extension module numbered K100 attached at the left
hand side of PLC. (See 4.3 for more details.)
•
After the program is being executed, all the previous network settings in DVPEN01-SL will be
modified into new settings.
3. If DVPEN01-SL is damaged, please change to a new DVPEN01-SL. The default IP for
DVPEN01-SL is 192.168.1.5.
4. Execute STOP
→
RUN in the new DVPEN01-SL and search for it again. We can see the IP has
been modified into 192.168.0.4.
6.4 Setting up Password and Clearing Password
Application
Setting up and clearing password by WPLSoft
Network
requirement
(1) Set password in DVPEN01-SL
(2) Unlock DVPEN01-SL
(3) Clear the password in DVPEN01-SL
1. See 6.1 for the connection and how to set up the communication.
2. Open the setup page and switch to “Password” page.
3. Check “Modify” box and enter “aabb” in “New Password” and “Confirm Password" columns. Click on
“OK” to save the password.