DVP-PLC Operation Manual
15
12. Set “Length of input data” parameter to “2 words”, “Length of output” to “2 words”, “Data_in[1]”
to “8449” (converted from VFD-C2000 status word H2101), “Data_in[2]” to “8451” (converted
from VFD-C2000 output frequency H2103), “Data_out[1]” to “8192” (converted from
VFD-C2000 control word H2000” and “Data_out[2]” to “8193” (converted VFD-C2000 given
frequency H2001). After all the settings are done, select “All Values” and click “Write”.
13. After the download is completed, re-power VFD-C2000.
Configuring DVPDNET-SL scanner module
1. Double click DNET Scanner (node 01) to open the “Scanner Module configuration…” dialog
box. We can now find the node VFD-C2000 Drives on the left-hand side table and an empty
scan list on the right hand side.