Chapter 5 Parameters
|
VFD-S Series
Revision August 2006, SE08, SW V2.61
5-9
Group 7 Motor Parameters
Pr. Explanation
Settings
Factory
Setting
NOTE
7-00 Motor Rated Current
d30 to d120%
d85
7-01
Motor No-Load Current
d0 to d90%
d50
7-02
Torque Compensation
d0 to d10
d1
7-03 Slip Compensation
d0.0 to d10.0
d0.0
Group 8 Special Parameters
Pr. Explanation
Settings
Factory
Setting
NOTE
8-00
DC Braking Voltage Level
d0 to d30%
d0
8-01
DC Braking Time during Start-Up
d0.0 to d60.0 Sec
d0.0
8-02
DC Braking time during Stopping
d0.0 to d60.0 Sec
d0.0
8-03
Start-Point for DC Braking
d0.0 to d400 Hz
d0.0
d0: Operation stops after
Momentary Power Loss
d1: Operation continues after
momentary power loss, speed
search starts with the Master
Frequency reference value
8-04
Momentary Power Loss Operation
Selection
d2: Operation continues after
momentary power loss, speed
search starts with the minimum
frequency
d0
8-05
Maximum Allowable Power Loss Time d0.3 to d5.0 Sec
d2.0
8-06
B.B. Time for Speed Search
d0.3 to d5.0 Sec
d0.5
8-07
Current Limit for Speed Search
d30 to d200%
d150
8-08
Skip Frequency 1 Upper Limit
d0.0 to d400 Hz
d0.0
8-09
Skip Frequency 1 Lower Limit
d0.0 to d400 Hz
d0.0
8-10
Skip Frequency 2 Upper Limit
d0.0 to d400 Hz
d0.0
8-11
Skip Frequency 2 Lower Limit
d0.0 to d400 Hz
d0.0
8-12
Skip Frequency 3 Upper Limit
d0.0 to d400 Hz
d0.0
8-13
Skip Frequency 3 Lower Limit
d0.0 to d400 Hz
d0.0
8-14
Auto Restart After Fault
d0 to d10
d0
d0: Enable
d1: Disable
8-15 AVR
Function
d2: Disable when deceleration
d2
115V/230V series: d350 to d450V
d380
8-16
Software Braking Level
460V series: d700 to d900V
d760
8-17
DC Braking Lower Bound Limit
d0.0 to d400 Hz
d0.0