Chapter 5 Parameters
|
VFD-S Series
Revision August 2006, SE08, SW V2.61
5-51
1
2
3
4
5
6
7
Weights
Bit
0=Forward
1=Reverse
Direction of 1st
Pr.5-00 =FWD
speed for
Direction of 2nd
Pr.5-01 =REV
speed for
Direction of 3rd
Pr.5-02 = F
speed for
Direction of 4th
Pr.5-03 = F
speed for
Direction of 5
Pr.5-04 = F
th speed for
Direction of 6
Pr.5-05 = REV
th speed for
Direction of 7
Pr.5-06 = F
th speed for
0
0
1
0
0
1
1
0
0
Direction
WD
WD
WD
WD
WD
The setting value = bit7 x 2
7
+bit6 x 2
6
+bit5 x 2
5
+bit4 x 2
4
+bit3 x 2
3
+bit2 x 2
2
+bit1 x 2
1
+bit0 x 2
0
= 0 x 2
7
+1 x 2
6
+0 x 2
5
+0 x 2
4
+0 x 2
3
+1 x 2
2
+0 x 2
1
+0 x 2
0
= 0+64+0+0+0+4+0+0
= 68
Setting Pr.5-08 as d68.
5-09
Time Duration of Zero Step Speed
Unit: 1
5-10
Time Duration of 1st Step Speed
Unit: 1
5-11
Time Duration of 2nd Step Speed
Unit: 1
5-12
Time Duration of 3rd Step Speed
Unit: 1
5-13
Time Duration of 4th Step Speed
Unit: 1
5-14
Time Duration of 5th Step Speed
Unit: 1
5-15
Time Duration of 6th Step Speed
Unit: 1
5-16
Time Duration of 7th Step Speed
Unit: 1
Settings
d0 to d65500
Factory Setting: d0
Pr.5-10 to Pr.5-16 correspond to operation time of each multi-step speed defined by
parameters 5-00 to 5-06. The maximum value of these parameters is 65500 sec., and it’s
displayed as d65.5.
NOTE
If a parameter is set to “d0” (0 Sec), the corresponding step will be skipped. This is commonly used
to reduce number of program steps.