![Delta Electronics AC Motor Drive VFD-E Скачать руководство пользователя страница 151](http://html1.mh-extra.com/html/delta-electronics/ac-motor-drive-vfd-e/ac-motor-drive-vfd-e_user-manual_2476007151.webp)
Chapter 4 Parameters
|
4-98
Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11
The motor auto tune procedure will set this parameter. The user may also set this parameter
without using Pr.07.04.
07.06
Motor Rated Slip (Motor 0)
Unit: 0.01
Settings
0.00 to 20.00Hz
Factory Setting: 3.00
Refer to the rated rpm and the number of poles on the nameplate of the motor and use the
following equation to calculate the rated slip.
Rated Slip (Hz) = F
base
(Pr.01.01 base frequency) – (rated rpm x motor pole 120)
07.07
Slip Compensation Limit
Unit: 1
Settings
0 to 250%
Factory Setting: 200
This parameter sets the upper limit of the compensation frequency (the percentage of
Pr.07.06).
Example: when Pr.07.06=5Hz and Pr.07.07=150%, the upper limit of the compensation
frequency is 7.5Hz. Therefore, for a 50Hz motor, the max. output is 57.5Hz.
07.08
Torque Compensation Time Constant
Unit: 0.01
Settings
0.01 ~10.00 sec
Factory Setting: 0.10
07.09
Slip Compensation Time Constant
Unit: 0.01
Settings
0.05 ~10.00 sec
Factory Setting: 0.20
Setting Pr.07.08 and Pr.07.09 changes the response time for the compensations.
Too long time constants give slow response; too short values can give unstable operation.
07.10
Accumulative Motor Operation Time (Min.)
Unit: 1
Settings
0~1439
Factory Setting: 0
07.11
Accumulative Motor Operation Time (Day)
Unit: 1
Settings
0 ~65535
Factory Setting: 0
Pr.07.10 and Pr.07.11 are used to record the motor operation time. They can be cleared by
setting to 0 and time is less than 1 minute is not recorded.
07.12
Motor PTC Overheat Protection
Unit: 1
Factory Setting: 0
Settings
0
Disable
1
Enable
07.14
Motor PTC Overheat Protection Level
Unit: 0.1
Содержание AC Motor Drive VFD-E
Страница 1: ......
Страница 2: ......
Страница 3: ......
Страница 13: ...This page intentionally left blank...
Страница 27: ...Chapter 1 Introduction 1 14 Revision June 2008 04EE SW PW V1 11 CTL V2 11 This page intentionally left blank...
Страница 233: ......
Страница 237: ...Appendix A Specifications A 4 Revision June 2008 04EE SW PW V1 11 CTL V2 11 This page intentionally left blank...
Страница 272: ...Appendix B Accessories Revision June 2008 04EE SW PW V1 11 CTL V2 11 B 35 B 11 DIN Rail B 11 1 MKE DRA...
Страница 274: ...Appendix B Accessories Revision June 2008 04EE SW PW V1 11 CTL V2 11 B 37...
Страница 275: ...Appendix B Accessories B 38 Revision June 2008 04EE SW PW V1 11 CTL V2 11 This page intentionally left blank...
Страница 349: ...Appendix D How to Use PLC Function D 66 Revision June 2008 04EE SW PW V1 11 CTL V2 11 This page intentionally left blank...