Chapter 4 Parameters
|
4-60
Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11
02.16
Display the Master Freq Command Source
Settings
Read Only
Factory setting: ##
You can read the master frequency command source by this parameter.
Display Value
Bit
Function
1
Bit0=1 Master Freq Command Source by First Freq Source (Pr.02.00).
2
Bit1=1 Master Freq Command Source by Second Freq Source (Pr.02.09).
4
Bit2=1 Master Freq Command Source by Multi-input function
8 Bit3=1
Master Freq Command Source by PLC Freq command
(NOT for VFD*E*C models)
02.17
Display the Operation Command Source
Settings
Read Only
Factory setting: ##
You can read the operation source by this parameter.
Display Value
Bit
Function
1
Bit0=1 Operation Command Source by Digital Keypad
2
Bit1=1 Operation Command Source by RS485 communication
4
Bit2=1 Operation Command Source by External Terminal
8
Bit3=1 Operation Command Source by Multi-input function
16 Bit4=1
Operation Command Source by PLC Operation Command
(NOT for VFD*E*C models)
Содержание AC Motor Drive VFD-E
Страница 1: ......
Страница 2: ......
Страница 3: ......
Страница 13: ...This page intentionally left blank...
Страница 27: ...Chapter 1 Introduction 1 14 Revision June 2008 04EE SW PW V1 11 CTL V2 11 This page intentionally left blank...
Страница 233: ......
Страница 237: ...Appendix A Specifications A 4 Revision June 2008 04EE SW PW V1 11 CTL V2 11 This page intentionally left blank...
Страница 272: ...Appendix B Accessories Revision June 2008 04EE SW PW V1 11 CTL V2 11 B 35 B 11 DIN Rail B 11 1 MKE DRA...
Страница 274: ...Appendix B Accessories Revision June 2008 04EE SW PW V1 11 CTL V2 11 B 37...
Страница 275: ...Appendix B Accessories B 38 Revision June 2008 04EE SW PW V1 11 CTL V2 11 This page intentionally left blank...
Страница 349: ...Appendix D How to Use PLC Function D 66 Revision June 2008 04EE SW PW V1 11 CTL V2 11 This page intentionally left blank...