Chapter 4 Parameters
|
4-22
Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11
Parameter Explanation
Settings
Factory
Setting
Customer
0: Operation stops after momentary power
loss
1: Operation continues after momentary
power loss, speed search starts with the
Master Frequency reference value
08.04
Momentary Power
Loss Operation
Selection
2: Operation continues after momentary
power loss, speed search starts with the
minimum frequency
0
08.05
Maximum Allowable
Power Loss Time
0.1 to 5.0 sec
2.0
08.06
Base-block Speed
Search
0: Disable speed search
1: Speed search starts with last frequency
command
2: Starts with minimum output frequency
1
08.07
B.B. Time for Speed
Search
0.1 to 5.0 sec
0.5
08.08
Current Limit for
Speed Search
30 to 200%
150
08.09
Skip Frequency 1
Upper Limit
0.00 to 600.0 Hz
0.00
08.10
Skip Frequency 1
Lower Limit
0.00 to 600.0 Hz
0.00
08.11
Skip Frequency 2
Upper Limit
0.00 to 600.0 Hz
0.00
08.12
Skip Frequency 2
Lower Limit
0.00 to 600.0 Hz
0.00
08.13
Skip Frequency 3
Upper Limit
0.00 to 600.0 Hz
0.00
08.14
Skip Frequency 3
Lower Limit
0.00 to 600.0 Hz
0.00
08.15
Auto Restart After
Fault
0 to 10 (0=disable)
0
08.16
Auto Reset Time at
Restart after Fault
0.1 to 6000 sec
60.0
0: Disable
08.17
Auto Energy Saving 1: Enable
0
Содержание AC Motor Drive VFD-E
Страница 1: ......
Страница 2: ......
Страница 3: ......
Страница 13: ...This page intentionally left blank...
Страница 27: ...Chapter 1 Introduction 1 14 Revision June 2008 04EE SW PW V1 11 CTL V2 11 This page intentionally left blank...
Страница 233: ......
Страница 237: ...Appendix A Specifications A 4 Revision June 2008 04EE SW PW V1 11 CTL V2 11 This page intentionally left blank...
Страница 272: ...Appendix B Accessories Revision June 2008 04EE SW PW V1 11 CTL V2 11 B 35 B 11 DIN Rail B 11 1 MKE DRA...
Страница 274: ...Appendix B Accessories Revision June 2008 04EE SW PW V1 11 CTL V2 11 B 37...
Страница 275: ...Appendix B Accessories B 38 Revision June 2008 04EE SW PW V1 11 CTL V2 11 This page intentionally left blank...
Страница 349: ...Appendix D How to Use PLC Function D 66 Revision June 2008 04EE SW PW V1 11 CTL V2 11 This page intentionally left blank...