Chapter 5
Troubleshooting
|
5-10
Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11
4.
Store within a relative humidity range of 0% to 90% and non-condensing environment.
Use an air conditioner and/or exsiccator.
5.15 Affecting Other Machines
An AC motor drive may affect the operation of other machines due to many reasons. Some solutions
are:
High Harmonics at Power Side
High harmonics at power side during running can be improved by:
1.
Separate the power system: use a transformer for AC motor drive.
2.
Use a reactor at the power input terminal of the AC motor drive.
3.
If phase lead capacitors are used (never on the AC motor drive output!!), use serial
reactors to prevent damage to the capacitors damage from high harmonics.
serial reactor
phase lead capacitor
Motor Temperature Rises
When the motor is a standard induction motor with fan, the cooling will be bad at low speeds,
causing the motor to overheat. Besides, high harmonics at the output increases copper and
core losses. The following measures should be used depending on load and operation
range.
1.
Use a motor with independent ventilation (forced external cooling) or increase the motor
rated power.
2.
Use a special inverter duty motor.
3.
Do NOT run at low speeds for long time.
Содержание AC Motor Drive VFD-E
Страница 1: ......
Страница 2: ......
Страница 3: ......
Страница 13: ...This page intentionally left blank...
Страница 27: ...Chapter 1 Introduction 1 14 Revision June 2008 04EE SW PW V1 11 CTL V2 11 This page intentionally left blank...
Страница 233: ......
Страница 237: ...Appendix A Specifications A 4 Revision June 2008 04EE SW PW V1 11 CTL V2 11 This page intentionally left blank...
Страница 272: ...Appendix B Accessories Revision June 2008 04EE SW PW V1 11 CTL V2 11 B 35 B 11 DIN Rail B 11 1 MKE DRA...
Страница 274: ...Appendix B Accessories Revision June 2008 04EE SW PW V1 11 CTL V2 11 B 37...
Страница 275: ...Appendix B Accessories B 38 Revision June 2008 04EE SW PW V1 11 CTL V2 11 This page intentionally left blank...
Страница 349: ...Appendix D How to Use PLC Function D 66 Revision June 2008 04EE SW PW V1 11 CTL V2 11 This page intentionally left blank...