VFD-F Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
8-16
Group 9 Communication Parameters
Parameters Functions
Settings
Factory
Setting
Customer
a
09-00 Communication
Address
01-254
00:Disable
01
a
09-01 Transmission Speed (Baud
Rate)
00: Baud rate 4800
01: Baud rate 9600
02: Baud rate 19200
03: Baud rate 38400
01
a
09-02 Transmission Fault Treatment 00: Warn and keep operating
01: Warn and RAMP to stop
02: Warn and COAST to stop
03: No warning and no
display
03
09-03 Over
Time
Detection
during
Transmission
00: Disable
01: Enable
00
09-04 Communication Format
00: 7-bit for ASCII
01: 8-bit for ASCII
02: 8-bit for RTU
00
09-05 Even/Odd
Parity
and
Stopping
Parity Setting
00: None 2 stop bit
01: Even 2 stop bit
02: Odd 2 stop bit
03: None 1 stop bit
04: Even 1 stop bit
05: Odd 1 stop bit
00
a
09-06 Communication
Operation
Command 1
Bit0~1: 00: Disable
01: Stop
10: Start-up
11: JOG start-up
Bit2~3: Reserved
Bit4~5: 00: No function
01: FWD command
10: REV command
11: Change direction
command
Bit6~7: 00: 1
st
step
accel/decel speed
01: 2
nd
step
accel/decel speed
10: 3
rd
step
accel/decel speed
11: 4
th
step
accel/decel speed
00
Содержание AC Drive VFD-F Series
Страница 1: ......
Страница 2: ......
Страница 3: ......
Страница 107: ...VFD F Series DELTA ELECTRONICS INC ALL RIGHTS RESERVED This page intentionally left blank...
Страница 133: ...VFD F Series DELTA ELECTRONICS INC ALL RIGHTS RESERVED This page intentionally left blank...
Страница 142: ...B VFD F Series DELTA ELECTRONICS INC ALL RIGHTS RESERVED B 7 Figure 2 VFDB4132 VFDB4132 CHARGE ACT OC OH...
Страница 161: ...VFD F Series DELTA ELECTRONICS INC ALL RIGHTS RESERVED C 8 KPF CC01 Unit mm inches...