VFD-F Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-16
Setting Functions
Descriptions
21
Low voltage detection
The corresponding output will be closed when
the DC Bus voltage drops below our threshold.
The keypad will display “Lu”.
22
Operation Mode indication
The corresponding output will be closed when
the AC drives “Operation Command” is
controlled by the external terminals.
23
Fault Indication
The corresponding output will be closed when
AC drive has experienced a fault.
24
Master Frequency Attained 1
The corresponding output will be closed when
the AC drives output frequency exceeds
(Pr.03-08) Master Frequency Attained 1.
25
Master Frequency Attained 2
The corresponding output will be closed when
the AC drives output frequency exceeds
(Pr.03-09) Master Frequency Attained 2.
26 Over
Temperature
indication
The
corresponding output will be closed when
the AC drive temperature exceeds its rating.
27
Drive Ready
The corresponding output will be closed the
when the AC drive is ready and has no faults.
28
External Emergency Stop (EF1)
The corresponding output will be closed when
multi-function input terminals (Pr.04-00 to
04-07) are set to emergency stop and then
activated.
29
Software brake output
The corresponding output will be closed when
the AC drives DC bus voltage exceeds
(Pr.08-19) the brake level.
30
OL or OL1 overload warning
The corresponding output will be closed upon
an overload (OL or OL1) fault.
31
Dwell indication (sleep)
The corresponding output will be closed when
the AC drive is in a Dwell status (Pr.11-07).
32
Low current indication
The corresponding output will be closed when
the AC drives output current is lower than the
Low Current setting (Pr.06-08).
33
PID feedback error indication
The corresponding output will be closed when
the PID feedback signal has an error.
34
PLC Program Running
The Output will be activated when PLC
Program is running.
35
PLC Program Step Completed
The Output will be activated for 0.5 sec when
each multi-step speed is attained.
36 PLC
Program
Completed
The output will be activated for 0.5 sec when
the PLC program cycle has completed
37 PLC
Operation
Paused
The output will be activated when PLC
operation is paused.
The VFD-F has two form C relays (multi-function output 1 and 2). There is an optional
External Relay Card with 6 NO contact relays (multi-function outputs 3-8).
Содержание AC Drive VFD-F Series
Страница 1: ......
Страница 2: ......
Страница 3: ......
Страница 107: ...VFD F Series DELTA ELECTRONICS INC ALL RIGHTS RESERVED This page intentionally left blank...
Страница 133: ...VFD F Series DELTA ELECTRONICS INC ALL RIGHTS RESERVED This page intentionally left blank...
Страница 142: ...B VFD F Series DELTA ELECTRONICS INC ALL RIGHTS RESERVED B 7 Figure 2 VFDB4132 VFDB4132 CHARGE ACT OC OH...
Страница 161: ...VFD F Series DELTA ELECTRONICS INC ALL RIGHTS RESERVED C 8 KPF CC01 Unit mm inches...