5
VFD-F Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-59
The explanation of exception codes:
Exception
code
Explanation
01
Illegal function code:
The function code received in the command message is not available for the AC
motor drive.
02
Illegal data address:
The data address received in the command message is not available for the AC
motor drive.
03
Illegal data value:
The data value received in the command message is not available for the AC
drive.
04
Slave device failure:
The AC motor drive is unable to perform the requested action.
10
Communication time-out:
If Pr.09-03 is not equal to 0.0, Pr.09-02=00~02, and there is no communication
on the bus during the Time-out detection period (set by Pr.09-03), “cE10” will be
shown on the keypad.