Local Outputs Tab
Page 31 of 67
eZV-440 Version 2.1 Application Guide
Document Edition 2.5
Set Up Actuator Damper Output
This section describes how to set up the actuator damper output.
To set up an actuator damper output:
1.
In the Function field, select VAV/VVT Damper.
2.
In the Control Source field, AirFlowDemand_ is selected automatically.
3.
In the Control Type field, select the method of control used on the damper signal.
For more information about control types, see
Appendix B Control Types
4.
If you are using an analog actuator, in the Action field, choose between direct or reverse
control. For tri-state actuators, use the Control Type field to set the damper’s open and
close direction.
5.
Click the “+” sign and in OP5-6Runtime, enter the amount of time it takes to move the
damper from fully open to fully closed positions.
6.
If you are setting up a tri-state actuator with damper feedback, set up damper feedback
on the Local Inputs tab in the configuration graphic.