Expert
Logger
These settings are dependent on the
Function code
inputs and also on
whether the channel is an input or output.
l
Data type
Specifies the data type for interpreting the transmitted payload data.
Bit
length, Byte order
and
Word order
are set and adjusted in relation to the
adopted setting.
Start position in payload data
are also set according to the data type.
l
Signed
Sets whether the integer data type is to be interpreted as signed or
unsigned. An 8-bit value would then be in the range -128 to 127 (two’s com-
plement) or 0 to 255. Floating values are always interpreted as signed. Bit-
values make no distinction between signed and unsigned.
l
Bit length
Sets the bit lengths for integer and floating data types.
Byte sequence
and
Word sequence
are adjusted according to length value. This also applies to
the numeric fields in the St
art position in data.
l
Encoding type
Displays the encoding type used for interpreting the transmitted payload
data.
l
Byte sequence
The byte order (byte sequence) is a number, made up of several bytes, that
sets how bytes are ordered for the address. BigEndian, also known as
Motorola format, orders the most significant byte to the lowest address.
LittleEndian, also known as Intel format, orders the least significant byte to
the lowest address. Refer also to
http://en.wikipedia.org/wiki/Endianness.
l
Word order
Like the byte order, word order orders word data (1 word = 2 bytes = 16
bits) to addresses. In addition to determining byte order, a different word
ordering may be necessary.
l
Byte pattern
(input channels only)
To display the different byte and word order combinations, a hex value (a ran-
dom number in the example) is shown with the resulting byte pattern of a
message.
Scaling
If a Modbus user sends values that require conversion, enable
Scaling
and
enter Min / Max values to convert from the Input
value
to the Scale value.
option is used, scaling takes place in the
opposite direction: Enter the range from the source data in
Scale
value
and the range for the output signal in
Output value
.
Without scaling, the channel's
Data type
is used When scaling is
enabled, the floating data type is always used for the channel.
This also applies when the channel is used as an output: When scal-
ing is enabled, the channel must have the floating data type, oth-
erwise you have to use the type under
Data type
.
221
Delphin Technology AG
Januar 2018
Expert
Logger
Manual
Содержание Expert Logger
Страница 1: ......
Страница 26: ...Expert Logger Sensor terminals Expert Logger 300 26 Delphin Technology AG Januar 2018 Expert Logger Manual ...
Страница 76: ...Expert Logger Main settings tab 76 Delphin Technology AG Januar 2018 Expert Logger Manual ...
Страница 84: ...Expert Logger 84 Delphin Technology AG Januar 2018 Expert Logger Manual ...
Страница 273: ...Expert Logger 8 Appendix 8 1 ISO 9001 certificate 273 Delphin Technology AG Januar 2018 Expert Logger Manual ...
Страница 274: ...Expert Logger 8 2 EC declaration on conformity 274 Delphin Technology AG Januar 2018 Expert Logger Manual ...
Страница 281: ...Expert Logger X XML network configuration template 37 281 Delphin Technology AG Januar 2018 Expert Logger Manual ...
Страница 282: ......