Note
Outside the standard operating temperature (10°C–35°C), the appliance can operate down to
–5°C or up to 45°C for a maximum of 1% of its annual operating hours. For temperatures
between 40°C and 45°C, de-rate maximum allowable temperature by 1°C per 125 m above 950
m (1°F per 228 ft).
Table 28 Expanded operating temperature specifications
Expanded operating temperature Specifications
Continuous operation
5°C to 40°C at 5% to 85% RH with 29°C dew
point.
Note
Outside the standard operating temperature (10°C
to 35°C), the appliance can operate continuously in
temperatures as low as 5°C and as high as 40°C.
For temperatures between 35°C to 40°C, de-rate
maximum allowable temperature by 1°C per 175 m
above 950 m (1°F per 319 ft).
≤ 1% of annual operating hours
–5°C to 45°C at 5% to 90% RH with 29°C dew
point.
Note
Outside the standard operating temperature (10°C
to 35°C), the appliance can operate down to –5°C
or up to 45°C for a maximum of 1% of its annual
operating hours.
For temperatures between 40°C and 45°C, de-rate
maximum allowable temperature by 1°C per 125 m
above 950 m (1°F per 228 ft).
Note
When operating in the expanded temperature range, appliance performance may be
impacted.
Note
When operating in the expanded temperature range, ambient temperature warnings
may be reported in the System Event Log.
Expanded operating temperature restrictions
l
Do not perform a cold startup below 5°C.
l
The operating temperature specified is for a maximum altitude of 3050 m (10,000
ft).
l
150 W/8 core, 165 W/12 core and higher wattage processor [Thermal Design
Power (TDP)>165 W] are not supported.
Technical specifications
34
VxRail Appliances on 14th Generation PowerEdge
P Series, V Series, and S Series Appliance Owner's Manual