Particulate
contamination
Specifications
Conductive dust
Air must be free of conductive dust, zinc whiskers, or other conductive particles.
NOTE:
This condition applies to data center and non-data center environments.
Corrosive dust
Air must be free of corrosive dust.
Residual dust present in the air must have a deliquescent point less than 60% relative humidity.
NOTE:
This condition applies to data center and non-data center environments.
Table 59. Gaseous contamination specifications
Gaseous contamination
Specifications
Copper coupon corrosion rate <300 Å/month per Class G1 as defined by ANSI/ISA71.04-2013
Silver coupon corrosion rate
<200 Å/month per Class G1 as defined by ANSI/ISA71.04-2013
NOTE:
Maximum corrosive contaminant levels measured at ≤50% relative humidity.
Relative humidity specifications
Table 60. Relative humidity specifications
Relative humidity
Allowable Operation
Temperature Ranges (For Altitude <900
meters or 2953 feet)
10 to 35°C (50 to 95°F) with no direct sunlight on the platform
Humidity Percent Ranges
8% RH with -12°C minimum dew point to 80% RH with 21°C (69.8°F) maximum dew
point
Operational Altitude De-Rating
Maximum temperature is reduced by 1°C/300 meters (1.8°F/984 feet) above 900
meters (2,953 feet)
Maximum vibration specifications
Table 61. Maximum vibration specifications
Maximum vibration
Specifications
Operating
0.26 Grms at 5 Hz to 350 Hz (all operation orientations).
Storage
1.88 Grms at 10 Hz to 500 Hz for 15 min (all six sides tested).
Maximum shock specifications
Table 62. Maximum shock specifications
Maximum shock
Specifications
Operating
Six consecutively executed shock pulses 6 G in the positive and negative x, y, z axis for up to 11 ms (four
pulses on each side of the system).
Storage
Six consecutively executed shock pulses in the positive and negative x, y, and z axis (one pulse on each
side of the system) of 71 G for up to 2 ms.