Never turn on any equipment when there is an evidence of fire, water or structural damage.

Delios DLX 500HV/600HV/800HV/1000HV

Quick Start Guide

Instructions

The installation must only be carried out only by qualified personnel. 
The operations described here must be carried out only by qualified 
installers.

The customer is civilly liable for the qualification and mental or 
physical state of the professional figures who operate this equipment. 
They must always use the personal protective equipment required by 
the laws of the country of destination and anything else provided to 
their employer.

Install the DLX in such a way as to have the LCD display at eye height.

The surface where the DLX will be installed must withstand its weight 
(25 kg).

To prevent the risk of electric shock or other injury, check that there 
are no electrical or hydraulic lines in the walls before drilling the 
mounting holes of the DLX.

Follow the installation steps to mount the DLX:

1.

Fix the top and bottom mounting brackets to the DLX 
body (Follow the instructions shown in Figure 2).

2.

Drill the holes to fix the DLX mounting support on the 
wall.

3.

Fix the mounting support to the wall.

4.

Install the DLX.

5.

Fix the DLX to the wall using the bottom bracket fixing 
screw.

Instructions

Delios installers are recommended to wear clothing and PPE provided 
by their employer. Operators must not wear clothes or accessories that 
could start fires or produce static electricity or any item of clothing that 
could affect personal safety. When carrying out any operation on the 
equipment, clothes and instruments must be suitably insulated.

Optimal operation of the DLX system is ensured at a maximum ambient 
temperature of 40 

°

C (104 

°

F).

Due to the various wall types, fixing the DLX system might differ from 
case to case: Use appropriate tools and screws for installation.

Make sure that there is enough free space for air circulation around 
the DLX system (500 mm from the bottom).

In case of missing accessories, contact Delios technical  support
representative.

DLX parts MUST NOT be energised during mounting and installation.

DLX can only be used with photovoltaic modules that meet the 
specific requirements of class A in accordance with the indications of 
the IEC 61730 standard.

Do not install the DLX in a position directly exposed to the sun.

The DLX must be installed indoor in a room with relative humidity 
ranging from 5 % to 95 % without condensation.

Do not mount the DLX system above or under flammable building 
materials.

Do not install the DLX system in areas where highly flammable 
substances are present.

Do not install the DLX system in areas subject to explosion hazard.

2. Mounting

1. Getting started

DELIOS

DLX Hybrid Inverter System 

Mar. 2022 

© 2022 Delios - All Rights Reserved

DLX must be installed only by a qualified personnel.

During installation, unplug DLX. Read and understand the safety warnings prior to installation.

Prior to the installation it is required to download (www.delios-srl.it/download-dlx-hv),
read, understand the step by step instructions from the latest DLX installation manual.

Figure 1

Figure 2

Содержание DLX 500HV

Страница 1: ...tica o qualsiasi capo di abbigliamento che possa influire sulla sicurezza personale Quando si effettua un operazione sull apparecchiatura gli indumenti e gli strumenti devono essere adeguatamente isol...

Страница 2: ...0 minuti L inverter contiene condensatori che necessitano di un tempo minimo per la scarica Collegare i fili di fase L1 L2 L3 neutro N e terra PE dell ingresso della rete AC alla morsettiera GRID risp...

Страница 3: ...ricity or any item of clothing that could affect personal safety When carrying out any operation on the equipment clothes and instrumentsmust be suitably insulated Optimal operation of the DLX system...

Страница 4: ...t other operations on the inverter for at least 10 minutes The inverter contains capacitors that need a minimum time to discharge Connect the phase L1 L2 L3 neutral N and earth PE wires of the AC grid...

Страница 5: ...protezioni o i coperchi possono essere rimossi solo 10 minuti dopo aver scollegato l inverter dall alimentatore per consentire ai suoi componenti di raffreddarsi e a scaricare eventuali dispositivi s...

Страница 6: ...DLX pu essere collegato alla rete di distribuzione solo nei paesi per i quali il sistema certificato L inverter DLX dotato di un contatto di messa a terra esterno che deve essere collegato al condutto...

Страница 7: ...of 40 C free of conductive contaminant NOTE The DLX system can only be installed by qualified personnel who needs to fully understand and apply provided safety instructions in order to avoid electrica...

Страница 8: ...ion network only in the countries which the system is certified for The DLX inverter is equipped with an external earthing contact which must be connected to the protective conductor in addition to th...

Отзывы: