Section 6
Trouble shooting
Part Number: 9291000 06/22 37
Parem.
Label Description
Min
Max
Default
U.M.
Type
U5
Duration of ozonizer activation (if U5=0, then key O3 is
disabled)
0
300
0
min
U6
Low pressure SW5 input polarity (0=N.O., 1=N.C.)
0
1
1
flag
U7
Low pressure alarm delay
0
999
30
sec
U8
Kriwan alarm SW4 input polarity
0
1
1
flag
U9
Kriwan alarm delay
0
999
5
sec
U10
Micro evap alarm SW2 input polarity (0=N.O., 1=N.C.)
0
1
1
flag
U11
Micro evap alarm delay
0
999
0
sec
U12
MaxP-Oil pressure - Magnetothermic switch alarm SW3 input
polarity (0=N.O., 1=N.C.)
0
1
1
flag
U13
MaxP-Oil pressure - Magnetothermic switch alarm delay
0
999
0
sec
U14
PR6 magnetothermic switch input configuration (0=on/off,
1=4-20 mA)
0
1
0
flag
UA
Value sampling range (with uA=0, then the HACCP key is
disabled)
0
99
10
min
UB
SW6 voltage alarm input polarity (0=N.O., 1=N.C.)
0
1
0
flag
UC
Voltage alarm delay
0
999
5
sec
UF
Micro-door alarm delay (only with the machine running)
0
99
5
min
UG
Compressor turning off delay from door opening
0
499
90
sec
UH
Maximum pressure alarm (above the pressure alarm increase
by 5 bar hysteresis)
10
30
27
bar
UL
Minimum interruption time for blackout alarm
0
99
10
min
UT
Minimum temp drop, with active door alarm, in the next 15
minutes of the door alarm, in order to disable the open door
alarm
0
30
5
°C
Temperature Alarms
A2
Delta T related to the set point, for over temperature alarms in
positive storage (if A2 = 0, no alarm)
0
90
0
°C
A4
Delta T related to the set point, for over temperature alarms in
negative storage (if A4 = 0, no alarm)
0
90
0
°C
A5
Over temperature alarm exclusion time from the beginning
of the storage or from the defrost end
0
240
30
min
A6
Over temperature alarm acquisition time
0
240
20
min
Configurations
M4
Setting the type of start-up chilling (if=0, the current one is
repeated upon turning off)
0
15
0
number
M5
Compressor pre-heating time
0
120
0
min
M6
SW1 output relay turning off delay - Cabinet light (if M6=0,
the output is managed as Alarm output)
0
999
300
sec
TEL
Service phone number (14 digits)
--------
----
number
Defrosting
SC1
Defrosting time
1
900
400
min
Содержание CV10E
Страница 3: ...THIS PAGE INTENTIONALLY LEFT BLANK Part Number 9291000 06 22 3 ...
Страница 11: ...THIS PAGE INTENTIONALLY LEFT BLANK Section 2 Specifications Part Number 929100 06 22 11 ...
Страница 17: ...Section 3 Installation Part Number 9291000 06 22 17 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 25: ...Section 4 Operation Part Number 9291000 06 22 25 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 39: ...Section 6 Trouble shooting Part Number 9291000 06 22 39 ...